An alternate oxic-anoxic process automatically controlled. Theory and practice in a real treatment plant network

被引:30
作者
Battistoni, P
Boccadoro, R
Bolzonella, D
Marinelli, M
机构
[1] Marche Polytech Univ, Fac Engn, Inst Hydraul, I-60131 Ancona, Italy
[2] Univ Verona, Dept Sci & Technol, I-37134 Verona, Italy
关键词
alternate process; dissolved oxygen; oxidation reduction potential; nutrient removal; wastewater treatment;
D O I
10.2166/wst.2004.0874
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
A simple mathematical model of an alternate oxic-anoxic process has been elaborated. It enables us to optimise the cycle time on the basis of maximum nitrates concentration in the effluent and the desired nitrogen removal performance. At the same time the model can be employed to verify the impact of the variations of flow rate and influent characteristics as well as the operational parameters of the process. Actually, the model confirms the process efficiency but its feasibility in real plants needs a local or remote process control. To verify these theoretical conclusions a real wastewater plant (700 PE) has been upgraded in an alternate oxic-anoxic process. It was implemented with software able to elaborate the data of dissolved oxygen concentration and oxidation reduction potential. Moreover, the evaluation of the flexing points was performed to manage mixer and blowers. A one-year experience of plant management allowed us to obtain very high nitrogen removal. However, the performances were different during wet or dry weather periods. The statistical analysis of probe signals evaluation confirmed the capability of the control device to detect the flexing points during the anoxic phase (70-94%). On the other hand, the capability of detecting the DO signal was lower, in particular when the oxygen demand was similar to the amount of supplied oxygen. The hourly variations of flow rate and mass loading determines different conditions for starting the anoxic phase: over aeration, over loading and the equivalence of oxygen demand and supply, are the main factors determining the blowers stopping.
引用
收藏
页码:337 / 344
页数:8
相关论文
共 13 条
  • [1] [Anonymous], STAND METH EX WAT WA
  • [2] INTERMITTENT AERATION FOR NITROGEN REMOVAL IN SMALL OXIDATION DITCHES
    ARAKI, H
    KOGA, K
    INOMAE, K
    KUSUDA, T
    AWAYA, Y
    [J]. WATER SCIENCE AND TECHNOLOGY, 1990, 22 (3-4) : 131 - 138
  • [3] An automatically controlled alternate oxic-anoxic process for small municipal wastewater treatment plants
    Battistoni, P
    De Angelis, A
    Boccadoro, R
    Bolzonella, D
    [J]. INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2003, 42 (03) : 509 - 515
  • [4] BATTISTONI P, 1999, Patent No. 000018
  • [5] BATTISTONI P, 2000, P INT S SAN ENV ENG
  • [6] DEGUIN A, 1992, INTERET PRATIQUE UTI
  • [7] Modified platinum electrodes: Electrochemical characteristics and behaviour in activated sludge
    Heduit, A
    Quinio, I
    Stadmuller, D
    Thevenot, DR
    [J]. WATER SCIENCE AND TECHNOLOGY, 1996, 34 (3-4) : 143 - 150
  • [8] HENZE M, 1998, WASTEWATER TREATMENT
  • [9] AUTOMATIC REGULATION OF ACTIVATED-SLUDGE AERATION - SINGLE-TANK NITRIFICATION-DENITRIFICATION
    LEFEVRE, F
    AUDIC, JM
    BUJON, B
    [J]. WATER SCIENCE AND TECHNOLOGY, 1993, 28 (10) : 289 - 298
  • [10] Process state evaluation of Alternating Oxic-Anoxic Activated Sludge using ORP, pH and DO
    Paul, E
    Plisson-Saune, S
    Mauret, M
    Cantet, J
    [J]. WATER SCIENCE AND TECHNOLOGY, 1998, 38 (03) : 299 - 306