General correlations for the heat and mass transfer coefficients in an air-solution contactor of a liquid desiccant system and an experimental case application

被引:24
作者
Varela, Richard Jayson [1 ]
Yamaguchi, Seiichi [2 ]
Giannetti, Niccolo [3 ]
Saito, Kiyoshi [3 ]
Harada, Masatoshi [4 ]
Miyauchi, Hikoo [4 ]
机构
[1] Waseda Univ, Dept Appl Mech, Shinjuku Ku, 3-4-1 Okubo, Tokyo 1698555, Japan
[2] Waseda Univ, Res Inst Sci & Engn, Shinjuku Ku, 3-4-1 Okubo, Tokyo 1698555, Japan
[3] Waseda Univ, Dept Appl Mech & Aerosp Engn, Shinjuku Ku, 3-4-1 Okubo, Tokyo 1698555, Japan
[4] Dyna Air Co Ltd, Chiyoda Ku, 3-4-2 Kanda, Tokyo 1010054, Japan
关键词
Heat transfer coefficient; Mass transfer coefficient; Nusselt number; Sherwood number; Air-solution contactor; Liquid desiccant system; CROSS-FLOW DEHUMIDIFIER; TRANSFER PERFORMANCE; LITHIUM-CHLORIDE;
D O I
10.1016/j.ijheatmasstransfer.2017.12.089
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents general types of correlation for the heat and mass transfer coefficients inside an air solution contactor as expressions of Reynolds-Prandtl numbers and Reynolds-Schmidt numbers, respectively. These general equations summarize the physical and thermophysical properties of the air, the solution, and the contactor, which make them capable to be used for parametric studies provided they are fitted in a wide range of experimental data that include all the properties involved. In this work, a liquid desiccant system with an adiabatic structured packed bed as contactor and an aqueous lithium chloride as solution was constructed. The experimental data taken at various air superficial velocities and solution flow rates were fitted to the general correlations, and comparisons between the predicted and experimental results for both coefficients are within +/- 10%, for both dehumidification and regeneration processes. In addition, the calculated values of the outlet air humidity ratio and temperature agree well with the experimental data for both processes. The particular equations for the heat and mass transfer coefficients can be used to perform parametric studies at different air superficial velocities and solution flow rates with very good accuracy. Results from this study can help improve the system design and operation methods of air-solution contactors. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:851 / 860
页数:10
相关论文
共 22 条
[1]  
ASHRAE, 2013, ASHRAE HDB FUND SI E
[2]  
Bird R. B., 2002, TRANSPORT PHENOMENA, P688
[3]   Thermodynamic properties of aqueous solutions of lithium chloride [J].
Chaudhari, SK ;
Patil, KR .
PHYSICS AND CHEMISTRY OF LIQUIDS, 2002, 40 (03) :317-325
[4]   Comparison between random and structured packings for dehumidification of air by lithium chloride solutions in a packed column and their heat and mass transfer correlations [J].
Chung, TW ;
Ghosh, TK ;
Hines, AL .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 1996, 35 (01) :192-198
[5]   PREDICTIONS OF MOISTURE REMOVAL EFFICIENCIES FOR PACKED-BED DEHUMIDIFICATION SYSTEMS [J].
CHUNG, TW .
GAS SEPARATION & PURIFICATION, 1994, 8 (04) :265-268
[6]  
Conde-Petit M.R., 2014, Aqueous Solutions of Lithium and Calcium Chlorides: Property Formulations for Use in Air Conditioning Equipment Design
[7]   GAS ABSORPTION ACCOMPANIED BY CHEMICAL REACTION [J].
DANCKWERTS, PV .
AICHE JOURNAL, 1955, 1 (04) :456-463
[8]   Experimental investigation on the heat and mass transfer between air and liquid desiccant in a cross-flow dehumidifier [J].
Gao, W. Z. ;
Liu, J. H. ;
Cheng, Y. P. ;
Zhang, X. L. .
RENEWABLE ENERGY, 2012, 37 (01) :117-123
[9]   Wetting behavior of a liquid film on an internally-cooled desiccant contactor [J].
Giannetti, Niccolo ;
Yamaguchi, Seiichi ;
Saito, Kiyoshi .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 101 :958-969
[10]   Entropy parameters for desiccant wheel design [J].
Giannetti, Niccolo ;
Rocchetti, Andrea ;
Saito, Kiyoshi ;
Yamaguchi, Seiichi .
APPLIED THERMAL ENGINEERING, 2015, 75 :826-838