Experimental study and correlations for heat and mass transfer coefficients in the dehumidifier of a frost-free heat pump system

被引:26
作者
Su, Wei [1 ]
Li, Weihao [1 ]
Sun, Bo [1 ]
Zhang, Xiaosong [1 ,2 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Jiangsu, Peoples R China
[2] Southeast Univ, Key Lab Energy Thermal Convers & Control, Minist Educ, Nanjing 210096, Jiangsu, Peoples R China
基金
中国国家自然科学基金;
关键词
Frost-free; Low humidity ratio; Correlation equations; Liquid desiccant; LIQUID DESICCANT DEHUMIDIFICATION; AIR-CONDITIONING SYSTEM; PERFORMANCE ANALYSIS; ENERGY-EFFICIENT; FLOW; DRIVEN; MODEL; FIN;
D O I
10.1016/j.ijheatmasstransfer.2018.11.078
中图分类号
O414.1 [热力学];
学科分类号
摘要
Decreasing the humidity ratio of ambient air can effectively prevent the frosting on the evaporator and improve the heat capacity of heat pump in winter. This paper conducts an experimental study and theoretical analysis on the heat and mass transfer performance of the cross-flow dehumidifier in a frost-free heat pump system. A mathematical model for predicting the heat and mass transfer performance in the dehumidifier is developed, and solved by finite difference method. Experimental study is carried out to analyze the influence of key parameters, including inlet air temperature, humidity ratio and flow rate, solution temperature, concentration and flow rate, on the coupled heat and mass transfer performance under low temperature and humidity ratio conditions. Based on the mathematical models and experimental results, the correlations of heat and mass transfer coefficients are proposed, and the deviations are within +/- 20%. Moreover, the effects of the inlet conditions of the liquid desiccant and air on the heat and mass transfer performance are compared with the experimental results reported in literature. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:450 / 462
页数:13
相关论文
共 36 条
[21]   Suggested solution concentration for an energy-efficient refrigeration system combined with condensation heat-driven liquid desiccant cycle [J].
She, Xiaohui ;
Yin, Yonggao ;
Zhang, Xiaosong .
RENEWABLE ENERGY, 2015, 83 :553-564
[22]   Experimental research on heat and mass transfer characteristics of cross-flow closed-type heat-source tower [J].
Song, Pengyuan ;
Wang, Baolong ;
Li, Xianting ;
Shi, Wenxing .
APPLIED THERMAL ENGINEERING, 2018, 135 :289-303
[23]   Feasibility of a two-stage liquid desiccant dehumidification system driven by low-temperature heat and power [J].
Su, Bosheng ;
Han, Wei ;
Sui, Jun ;
Jin, Hongguang .
APPLIED THERMAL ENGINEERING, 2018, 128 :795-804
[24]   Experimental investigation on a novel frost-free air source heat pump system combined with liquid desiccant dehumidification and closed-circuit regeneration [J].
Su, Wei ;
Li, Weihao ;
Zhou, Junming ;
Zhang, Xiaosong .
ENERGY CONVERSION AND MANAGEMENT, 2018, 178 :13-25
[25]   Simulation analysis of a novel no-frost air-source heat pump with integrated liquid desiccant dehumidification and compression-assisted regeneration [J].
Su, Wei ;
Li, Weihao ;
Zhang, Xiaosong .
ENERGY CONVERSION AND MANAGEMENT, 2017, 148 :1157-1169
[26]   Performance analysis of a novel frost-free air-source heat pump with integrated membrane-based liquid desiccant dehumidification and humidification [J].
Su, Wei ;
Zhang, Xiaosong .
ENERGY AND BUILDINGS, 2017, 145 :293-303
[27]   Thermodynamic analysis of a compression-absorption refrigeration air-conditioning system coupled with liquid desiccant dehumidification [J].
Su, Wei ;
Zhang, Xiaosong .
APPLIED THERMAL ENGINEERING, 2017, 115 :575-585
[28]   Performance analysis of a two-stage desiccant cooling system [J].
Tu, Rang ;
Liu, Xiao-Hua ;
Jiang, Yi .
APPLIED ENERGY, 2014, 113 :1562-1574
[29]   Investigation on the coupled heat and mass transfer process between extremely high humidity air and liquid desiccant in the counter-flow adiabatic packed tower [J].
Wang, Zhenying ;
Zhang, Xiaoyue ;
Li, Zhen .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 110 :898-907
[30]   Numerical study on the operating performances of a novel frost-free air-source heat pump unit using three different types of refrigerant [J].
Wang, Zhihua ;
Wang, Fenghao ;
Ma, Zhenjun ;
Song, Mengjie .
APPLIED THERMAL ENGINEERING, 2017, 112 :248-258