A Power Module for Grid Inverter With In-Built Short-Circuit Fault Current Capability

被引:28
|
作者
Shao, Weihua [1 ]
Wu, Ruizhu [2 ]
Ran, Li [1 ,2 ]
Jiang, Huaping [1 ]
Mawby, Philip A. [2 ]
Rogers, Daniel J. [3 ]
Green, Tim C. [4 ]
Coombs, Thomas [2 ]
Yardley, Kieran [2 ]
Kastha, Debaprasad [5 ]
Bajpai, Prabodh [5 ]
Zhou, Lin [1 ]
机构
[1] Chongqing Univ, Sch Elect Engn, Chongqing 400044, Peoples R China
[2] Univ Warwick, Sch Engn, Coventry CV4 7AL, W Midlands, England
[3] Univ Oxford, Dept Engn Sci, Oxford OX1 2JD, England
[4] Imperial Coll London, Dept Elect & Elect Engn, London SW7 2AZ, England
[5] IIT Kharagpur, Sch Energy Sci & Engn, Kharagpur 721302, W Bengal, India
基金
英国工程与自然科学研究理事会;
关键词
Phase change materials; Inverters; Fault currents; Heating systems; Synchronous generators; Insulated gate bipolar transistors; Circuit faults; IGBT power module; latent heat; overcurrent capability; packaging; phase change material; WIND TURBINES;
D O I
10.1109/TPEL.2020.2978656
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As grid codes evolve, inverter-interfaced renewable generation may be required to take greater responsibility for grid support. It may be obliged to source a large current during a short-circuit fault in the grid and provide large dynamic reactive power, beyond the inverter rating, for voltage recovery after the fault clearance. In this sense, the inverter-interfaced generating system would behave more similarly to a conventional synchronous machine. This is not yet mandatory but current technology cannot readily support it if required in the future, because the power semiconductors would overheat unless they are drastically derated. This study proposes a method to increase the power semiconductor's transient thermal capacity, and hence its short-term over-current capability, by integrating a phase-change material inside the power semiconductor module. Experiment and thermodynamic simulation across different materials are used to illustrate the feasibility of the concept and the factors that should be considered in such a design. The study shows that 1.5 p.u. (per unit) overcurrent could be achieved for 30 s, which is typical of synchronous generators; and 3.0 p.u. fault current could be achieved for 3 s. A custom-made 1200-V, 50-A IGBT half-bridge module integrating a liquid metal as the phase change material is compared with a conventional commercially available module. A validated simulation model is then used to further evaluate the proposal, regarding a 1700-V, 1000-A IGBT module for use in a wind turbine.
引用
收藏
页码:10567 / 10579
页数:13
相关论文
共 50 条
  • [21] A Current-Based Approach for Short-Circuit Fault Diagnosis in Closed-Loop Current Source Inverter
    Guo, Xiaoqiang
    Sui, Sen
    Wang, Baocheng
    Zhang, Wenlin
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (09) : 7941 - 7950
  • [22] The simulation study of the short-circuit current of the voltage source inverter
    Liu, H
    Chen, JY
    Shen, D
    Han, YD
    Li, CY
    Liu, YX
    Zhu, QX
    IECEC 96 - PROCEEDINGS OF THE 31ST INTERSOCIETY ENERGY CONVERSION ENGINEERING CONFERENCE, VOLS 1-4, 1996, : 507 - 512
  • [23] Reliability Enhancement of Power IGBTs under Short-Circuit Fault Condition Using Short-Circuit Current Limiting-Based Technique
    Mohsenzade, Sadegh
    Naghibi, Javad
    Mehran, Kamyar
    ENERGIES, 2021, 14 (21)
  • [24] Short-Circuit Characteristics and Impact of PV Inverter on the protection of Distribution Grid
    Shi Mingming
    Yuan Xiaodong
    Yuan Yubo
    Chen Bing
    Lv Zhenhua
    2014 17TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS), 2014, : 791 - 794
  • [25] A Critical Fault-Tolerant Inverter Based on Internal Evolutionary Short-Circuit Failure Mechanism of IGBT Module
    Dou, Zhifeng
    Yang, Yan
    Zheng, Anping
    Wang, Nan
    IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2022, 12 (12): : 1914 - 1921
  • [26] Calculation of minimal short-circuit current in parallel arrangement of cables for a three phase short-circuit fault
    Ksiazkiewicz, Andrzej
    Batura, Ryszard
    PRZEGLAD ELEKTROTECHNICZNY, 2019, 95 (05): : 124 - 128
  • [27] Short-circuit Fault Characteristics Analysis for the Overhead Line in MMC-HVDC Power Grid
    Xin, Guangming
    Wang, Peiran
    Wei, Xiaoran
    Xie, Huan
    Zhang, Shuo
    Cao, Tianzhi
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2941 - 2947
  • [28] Theoretical analysis of short-circuit capability of SiC power MOSFETs
    Shoji, Tomoyuki
    Soeno, Akitaka
    Toguchi, Hiroaki
    Aoi, Sachiko
    Watanabe, Yukihiko
    Tadano, Hiroshi
    JAPANESE JOURNAL OF APPLIED PHYSICS, 2015, 54 (04)
  • [29] Design Strategy of Z-source Inverter for Utilization of Power Semiconductors with Extremely Low Short-circuit Capability
    Takashima, Kaoru
    Iijima, Ryuji
    Mannen, Tomoyuki
    Isobe, Takanori
    Iwamuro, Noriyuki
    Tadano, Hiroshi
    45TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2019), 2019, : 4997 - 5002
  • [30] Analysis of Fault Recorder Data for Short-Circuit Current in a 500kV Busbar Short-Circuit Accident
    Cao, Wei
    Wang, Yong-sheng
    Liu, Bei
    Wang, Wei
    MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 1290 - +