Evaluation of air management system's thermal performance for superior cooling efficiency in high-density data centers

被引:101
作者
Cho, Jinkyun [2 ]
Kim, Byungseon Sean [1 ]
机构
[1] Yonsei Univ, Dept Architectural Engn, Seoul 120749, South Korea
[2] Samsung C&T Corp, Construct Technol Ctr, Seoul 137070, South Korea
关键词
Data center; Aisle partition system; Cooling efficiency; Re-circulation air; By-pass air; CFD modeling;
D O I
10.1016/j.enbuild.2011.04.025
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In a typical data center, large numbers of IT sever racks are arranged in multiple rows. In IT environments, in which extensive electronic hardware is air-cooled, cooling system inefficiencies result when heated exhaust air from equipment prematurely mixes with chilled coolant air before it is used for cooling. Mixing of chilled air before it is used with heated exhaust air results in significant cooling inefficiencies in many systems. Over-temperatures may not only harm expensive electronic equipment but also interrupt critical and revenue generating services. The cool shield is a cost effective aisle partition system used to contain the air in cold aisles and hot aisles of an IT server room. This paper focuses on the use of performance metrics for analyzing a vertical aisle partition system in high-density data centers. Performance metrics provide a great opportunity for the data center industry at large. They could form the foundation for a standardized way of specifying and reporting various cooling solutions. The Rack Cooling Index (RCI) is a measure of how well the system cools the IT servers within the manufacturers' specifications, and the Return Temperature Index (RTI) is a measure of the energy performance of the air-management system. Combined, they provide an opportunity to judge the performance of the aisle partition system in an objective way subsequent to comprehensive CFD modeling. (C) 2011 Elsevier B.V. All rights reserved.
引用
收藏
页码:2145 / 2155
页数:11
相关论文
共 20 条
[1]  
[Anonymous], 2002, P AIAA2002 3091 AM I
[2]   Efficient thermal management of data centers - Immediate and long-term research needs [J].
Bash, CE ;
Patel, CD ;
Sharma, RK .
HVAC&R RESEARCH, 2003, 9 (02) :137-152
[3]   Thermo-fluids provisioning of a high performance high density data center [J].
Beitelmal, Abdlmonem H. ;
Patel, Chandrakant D. .
DISTRIBUTED AND PARALLEL DATABASES, 2007, 21 (2-3) :227-238
[4]   Cooling Systems for IT Environment Heat Removal in (Internet) Data Centers [J].
Cho, Jinkyun ;
Lim, Taisub ;
Kim, Byungseon Sean .
JOURNAL OF ASIAN ARCHITECTURE AND BUILDING ENGINEERING, 2008, 7 (02) :387-394
[5]   Measurements and predictions of the air distribution systems in high compute density (Internet) data centers [J].
Cho, Jinkyun ;
Lim, Taesub ;
Kim, Byungseon Sean .
ENERGY AND BUILDINGS, 2009, 41 (10) :1107-1115
[6]  
Emerson Network Power Energy logic, 2008, EN LOG RED DAT CENT
[7]  
Herrlin M.K., 2005, BUILD ENG, V111, P1
[8]  
Herrlin M.K., 2001, GR3028CORE NEBS THER
[9]  
Herrlin M.K., 2008, ASHRAE T, V114
[10]  
Herrlin M.K., 2007, Digit. Power Forum, P10