Improved Passivity-based Control Method of Grid-connected PV Inverter in Weak Grids

被引:0
作者
Liu Guihua [1 ]
Wang Wenxiu [1 ]
Zhu Xiaohui [1 ]
Wang Wei [1 ]
机构
[1] Harbin Inst Technol, Harbin, Heilongjiang, Peoples R China
来源
2018 21ST INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS) | 2018年
基金
中国国家自然科学基金;
关键词
weak grids; improved passivity-based control method; robustness; CONTROL STRATEGY;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
With the continuous increase in the penetration rate of photovoltaics (PV), the operating environment of the power grid becomes more and more complex. Weak grids usually present electrical characteristics like high harmonic content, high grid impedance and fluctuating voltage. When a grid-connected PV inverter is connected to weak grids, the traditional control method shows its limitation. In view of the nonlinearity of the mathematical model of the PV inverters, the algorithm derived from passive-based control (PBC) theory can be used to control the PV inverter, enabling the inverter to have better performance in weak grids. Firstly, this paper establishes the Euler-Lagrange (EL) mathematical model of the inverter based on energy method, and proves the passivity of the inverter system. Secondly, passivity-based control is applied to design the traditional passivity-based controller of the inverter system by injecting damping; then an improved passivity control method based on quasi-PR control method is proposed, namely, the error energy is first sent to the quasi-PR controller to change the damping coefficient of the system, then the coefficient is send to a conventional passivity-based controller to achieve the improved passivity-based control method. Finally, experimental comparison of the two methods show that the improved passivity-based control method is more suitable for weak grids with voltage instability and large impedance. The experimental results verify that the improved passivity-based control has strong robustness when the voltage fluctuates.
引用
收藏
页码:1151 / 1156
页数:6
相关论文
共 50 条
  • [21] Grid-Connected Inverter Output Impedance Reshaping for Passivity Enhancement and Disturbance Rejection
    Bian, Zhiwei
    Peng, Yuqi
    He, Yuanbin
    Hang, Lijun
    Xie, Xiaogao
    Chung, Henry Shu-Hung
    [J]. IEEE ACCESS, 2021, 9 : 118334 - 118345
  • [22] Comparison Study of MPPT Control Strategies for Double-stage PV Grid-connected Inverter
    Wang, Yubin
    Yu, Xichang
    [J]. 39TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2013), 2013, : 1561 - 1565
  • [23] Small-Signal Model and Control of PV Grid-Connected Micro Inverter Based on Interleaved Parallel Flyback Converter
    Zhao, Qiqi
    Fang, Yu
    Wang, Zhibin
    Xie, Yong
    [J]. PROCEEDINGS OF 2013 CHINESE INTELLIGENT AUTOMATION CONFERENCE: INTELLIGENT AUTOMATION & INTELLIGENT TECHNOLOGY AND SYSTEMS, 2013, 255 : 595 - 602
  • [24] SLIDING MODE CONTROL STRATEGY FOR QUASI-Z-SOURCE INVERTER IN PV GRID-CONNECTED SYSTEM
    Tian L.
    Yang X.
    [J]. Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (03): : 443 - 449
  • [25] Analysis of control strategy for grid-connected inverter under different constraints based on asymmetric grid
    Jiang, Weidong
    Wu, Zhiqing
    Hu, Yang
    Tao, Ziran
    [J]. Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2015, 39 (19): : 113 - 120and136
  • [26] Grid-Connected Converters: A Brief Survey of Topologies, Output Filters, Current Control, and Weak Grids Operation
    Hollweg, Guilherme V.
    Khan, Shahid A.
    Chaturvedi, Shivam
    Fan, Yaoyu
    Wang, Mengqi
    Su, Wencong
    [J]. ENERGIES, 2023, 16 (09)
  • [27] A Passivity-Based Weighted Proportional-Derivative Feedforward Scheme for Grid-Connected Inverters With Enhanced Harmonic Rejection Ability
    Wang, Cheng
    Wang, Xuehua
    He, Yuying
    Ruan, Xinbo
    [J]. IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2023, 11 (04) : 3656 - 3668
  • [28] Optimal passive LCL filter design for grid-connected converters in weak grids
    Abbas, Hayder Hassan
    Shafiee, Qobad
    Bevrani, Hassan
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2024, 235
  • [29] A Hybrid Multiresonances Suppression Method for Nonsynchronous LCL-Type Grid-Connected Inverter Clusters Under Weak Grid
    Liu, Jiang
    Sun, Xiangdong
    Chen, Zechi
    Chi, Yongchao
    Song, Weizhang
    Zhu, Qun
    Wheeler, Patrick
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2024, 39 (05) : 5386 - 5399
  • [30] Control Strategy for Photovoltaic Grid-connected Inverter with LCL Filter
    Zhang Guoyue
    Yin Ke
    Wu Yue
    Qi Donglian
    [J]. 26TH CHINESE CONTROL AND DECISION CONFERENCE (2014 CCDC), 2014, : 4770 - 4774