Adaptive Single-Pole Auto-Reclosing Scheme for Hybrid MMC-HVDC Systems

被引:65
作者
Wang, Ting [1 ]
Song, Guobing [1 ]
Hussain, Kazmi Sayed Tassawar [1 ]
机构
[1] Xi An Jiao Tong Univ, Dept Elect Engn, Xian 710049, Shaanxi, Peoples R China
基金
国家重点研发计划;
关键词
Adaptive auto-reclosing; active injection; fault identification; hybrid MMC; line coupling; DC; PROTECTION; FAULTS;
D O I
10.1109/TPWRD.2019.2921674
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
After the isolation of a single pole-to-ground fault, the adaptive auto-reclosing concept in high-voltage dc (HVDC) systems is difficult to be applied due to little coupling between the poles. With fault ride through capability, the hybrid modular multi-level converter (MMC) can be advantageous for future HVDC projects. This research proposes an adaptive auto-reclosing operation for hybrid MMC-based bipolar HVDC systems, based on fault identification by characteristic signal injection. The proposed method is based on voltage controllability of healthy pole MMC to inject dc voltage perturbations. Healthy line perturbations result in the induced characteristic signals to the faulty line, which contain information about the fault property. An additional control strategy for hybrid MMC, to inject signals with suitable amplitude and frequency, is also discussed in detail. Then, fault identification is realized by wavelet transform of traveling waves caused by the signal injection. Finally, a dc adaptive single-pole auto-reclosing scheme is proposed to shorten the reclose time and to distinguish between temporary faults and permanent faults. Simulation results verify the effectiveness of the proposed method in PSCAD/EMTDC software.
引用
收藏
页码:2194 / 2203
页数:10
相关论文
共 26 条
[1]  
[Anonymous], P IEEE INT EN C
[2]   Single pole-to-ground fault location method for MMC-HVDC system using active pulse [J].
Bi, Tianshu ;
Wang, Shuai ;
Jia, Ke .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (02) :272-278
[3]   Detection of high impedance faults using current transformers for sensing and identification based on features extracted using wavelet transform [J].
Chen, Jichao ;
Phung, Toan ;
Blackburn, Trevor ;
Ambikairajah, Eliathamby ;
Zhang, Daming .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (12) :2990-2998
[4]   A Comprehensive AC-Side Single-Line-to-Ground Fault Ride Through Strategy of an MMC-Based HVDC System [J].
Cui, Shenghui ;
Lee, Hak-Jun ;
Jung, Jae-Jung ;
Lee, Younggi ;
Sul, Seung-Ki .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2018, 6 (03) :1021-1031
[5]   Comparison of Secondary Arcs for Reclosing Applications [J].
Dias, O. ;
Magrin, F. ;
Tavares, M. C. .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (03) :1592-1599
[6]   Comparison between traditional single-phase auto reclosing and adaptive technique based on harmonic content measurement [J].
Dias, Ozenir ;
Tavares, Maria Cristina .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (04) :905-914
[7]   Transient Characteristics Under Ground and Short-Circuit Faults in a ±500 kV MMC-Based HVDC System With Hybrid DC Circuit Breakers [J].
Han, Xue ;
Sima, Wenxia ;
Yang, Ming ;
Li, Licheng ;
Yuan, Tao ;
Si, Yan .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (03) :1378-1387
[8]   Detection of secondary arc extinction for adaptive single phase auto-reclosing based on local voltage behaviour [J].
Jamali, Sadegh ;
Baayeh, Arman Ghaderi .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (04) :952-958
[9]   Low-Energy Protection System for DC Grids Based on Full-Bridge MMC Converters [J].
Jovcic, Dragan ;
Lin, Weixing ;
Nguefeu, Samuel ;
Saad, Hani .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (04) :1934-1943
[10]  
Kong M., 2017, PROCEEDING 19 EUROPE, P1