摘要
A study was conducted to evaluate new and laboratory-aged samples of surge arresters and anchorage polymeric insulators, for 12 and 24 kV networks, which are used by the Rio Grande Energia (RGE). Power Utility Polymeric compounds were analyzed by Differential Scanning Calorimetry (DSC), Thermogravimetric Analysis (TG), Dynamic-Mechanic Analysis (DMA), Fourier Transformed Infrared Spectroscopy (FTIR) and Scanning Electronic Microscopy (SEM) to verify changes in the insulator properties due to degradation occurred during the experiments. The analyses were carried out before and after 6 months of aging in laboratory devices (weatherometer, 120 degrees C, salt spray, immersion in water). After the aging experiments, high-voltage electrical tests were also conducted: a radio interference voltage test and, simultaneously, the total and the internal leakage currents were measured to verify the surface degradation of the polymeric material used in the housing. The impulse current test was applied with current values close to 5, 10 and 30 kA, in order to force an internal degradation. Results showed that only surface degradation is detected at the polymer. The main properties of the parts were not affected by the aging. It confirms that polymer insulator and surge arrestor are appropriate for use in electricity distribution networks.
引用
收藏
页码:436 / 442
页数:7
相关论文
共 6 条
  • [1] Multi-stress Aging Studies on Polymeric Surge Arresters for HVDC Transmission
    Gupta, Pranjal
    Reddy, G. Nithin
    Reddy, Subba B.
    PROCEEDINGS OF 2021 5TH INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (IEEE CATCON 2021), 2021, : 176 - 180
  • [2] Accelerated aging test to determine the replacement criterion of distribution surge arresters
    Kim, JY
    Kim, CY
    Song, IK
    Moon, JD
    2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2: DEVELOPING NEW PERSPECTIVES, 2001, : 793 - 796
  • [3] Performance of distribution-class surge arresters under dry and artificial pollution conditions
    I. A. Metwally
    Electrical Engineering, 2011, 93 : 55 - 62
  • [4] Performance of distribution-class surge arresters under dry and artificial pollution conditions
    Metwally, I. A.
    ELECTRICAL ENGINEERING, 2011, 93 (01) : 55 - 62
  • [5] Multistress accelerated aging of polymer housed surge arresters under simulated coastal Florida conditions
    Sundararajan, R
    Soundarajan, E
    Mohammed, A
    Graves, J
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (01) : 211 - 226
  • [6] Clarification of leakage current suppression effect of polymeric insulators applied for 6.6 kv distribution lines under rapid contaminated conditions
    Homma H.
    Yaji K.
    Kabasawa Y.
    Sato T.
    IEEJ Transactions on Power and Energy, 2018, 138 (09) : 781 - 790