Sub-synchronous Oscillations in Power Systems Caused by Grid-connected Wind Farms-A Survey of Mechanism Studies

被引:26
作者
Chen, Chen [1 ]
Du, Wenjuan [1 ]
Wang, Haifeng [1 ]
Littler, Tim [2 ]
机构
[1] North China Elect Power Univ, Beijing 102206, Peoples R China
[2] Queens Univ Belfast, Belfast, Antrim, North Ireland
关键词
Doubly-fed induction generator (DFIG); impedance-based analysis; modal analysis; permanent magnetic synchronous generator (PMSG); sub-synchronous oscillation; SUBSYNCHRONOUS RESONANCE; STABILITY ANALYSIS; MODAL-ANALYSIS; SSR ANALYSIS; GENERATOR; MODEL; PLL; IMPACT; PMSGS; GATE;
D O I
10.17775/CSEEJPES.2018.00560
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Sub-synchronous oscillation (SSO) incidents caused by dynamic interaction between wind farms and power system grids can threaten safe and reliable operations. This paper investigates mechanism studies of SSOs in power systems induced by grid-connected wind farms. First, characteristics of several severe SSO incidents encountered by real power systems caused by grid-connected wind farms are introduced. Second, in terms of principles and responses, this paper illustrates the most commonly adopted mechanism investigation methods for SSOs, which include impedance-based analysis (IMA) and the openloop modal analysis (OMA) methods. Systematic reviews that summarize existing studies using the IMA and OMA methods are discussed in this paper. Furthermore, a discussion of the current research gaps in the investigation of SSOs in power systems caused by grid-connected wind farms is presented.
引用
收藏
页码:495 / 503
页数:9
相关论文
共 49 条
[1]  
Adams J., 2012, P TRANSM DISTR C EXP, P1, DOI DOI 10.1109/TDC.2012.6281678
[2]   Impact of Renewable Energy Sources on Steady-state Stability of Weak AC/DC Systems [J].
Aik, Denis Lee Hau ;
Andersson, Goran .
CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2017, 3 (04) :419-430
[3]   Understanding the Origin of Oscillatory Phenomena Observed Between Wind Farms and HVdc Systems [J].
Amin, Mohammad ;
Molinas, Marta .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2017, 5 (01) :378-392
[4]  
[Anonymous], 2017 INT SIB C CONTR
[5]  
[Anonymous], IEEE T POWER APPARAT
[6]   EXPERIENCE WITH HVDC - TURBINE-GENERATOR TORSIONAL INTERACTION AT SQUARE BUTTE [J].
BAHRMAN, M ;
LARSEN, EV ;
PIWKO, RJ ;
PATEL, HS .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (03) :966-975
[7]   Probabilistic Stability Analysis of Subsynchronous Resonance for Series-Compensated DFIG-Based Wind Farms [J].
Chen, Wuhui ;
Xie, Xiaorong ;
Wang, Danhui ;
Liu, Huakun ;
Liu, Hui .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (01) :400-409
[8]  
Du W., 2009, 2009 INT C SUSTAINAB, P1
[9]   Subsynchronous Interactions Induced by DFIGs in Power Systems Without Series Compensated Lines [J].
Du, Wenjuan ;
Chen, Chen ;
Wang, Haifeng .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2018, 9 (03) :1275-1284
[10]   Concept of Modal Repulsion for Examining the Sub-Synchronous Oscillations in Power Systems [J].
Du, Wenjuan ;
Wang, Yang ;
Wang, Haifeng ;
Fu, Qiang .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2018, 33 (04) :4614-4624