Waste heat recovery of power plant with large scale serial absorption heat pumps

被引:79
作者
Xu, Z. Y. [1 ]
Mao, H. C. [2 ]
Liu, D. S. [2 ]
Wang, R. Z. [1 ]
机构
[1] Shanghai Jiao Tong Univ, Inst Refrigerat & Cryogen, Shanghai 200240, Peoples R China
[2] Shuangliang Ecoenergy Syst Co Ltd, Jiangyin 214444, Peoples R China
基金
中国国家自然科学基金; 国家重点研发计划;
关键词
Absorption heat pump; Waste heat; Large scale; Power plant; District heating; THERMODYNAMIC PERFORMANCE; SINGLE-STAGE; HOT-WATER; TRANSFORMER; ENERGY; EXCHANGERS;
D O I
10.1016/j.energy.2018.10.052
中图分类号
O414.1 [热力学];
学科分类号
摘要
Large amount of waste heat is dissipated in industries, resulting in energy waste and environment pollution. Waste heat recovery with absorption heat pump is one of the attractive solutions. In this paper, we present the theoretical study and test of a power plant waste heat recovery system with large scale LiBr-water absorption heat pumps for district heating. Waste heat from steam condenser with temperature of similar to 35 degrees C is recovered by the absorption heat pumps driven by steam with pressure of similar to 0.25 MPa from the turbine. Heat output from the absorption heat pumps is used to preheat the return water of district heating network from similar to 45 degrees C to similar to 80 degrees C. The return water is further heated by the steam to similar to 105 degrees C for heating supply. Large temperature lift of the return water is achieved by the serial absorption heat pumps. Theoretical analysis of the system is presented, showing advantages compared to the conventional absorption heat pump and original heating supply system. On-site test showed that COP of 1.77 and heating capacity of 63.57 MW were achieved by one serial absorption heat pump, with waste heat inlet/outlet temperature of 34.63/28.33 degrees C and return water inlet/outlet temperature of 45.94/81.34 degrees C. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1097 / 1105
页数:9
相关论文
共 32 条
[1]   Assessment of an absorption heat pump coupled to a multi-effect distillation unit within AQUASOL project [J].
Alarcon-Padilla, Diego-Cesar ;
Garcia-Rodriguez, Lourdes ;
Blanco-Galvez, Julian .
DESALINATION, 2007, 212 (1-3) :303-310
[2]   Performance modelling of single and double absorption heat transformers [J].
Barragan Reyes, Rosa Maria ;
Arellano Gomez, Victor Manuel ;
Garcia-Gutierrez, Alfonso .
CURRENT APPLIED PHYSICS, 2010, 10 :S244-S248
[3]  
Barragan RM, 1998, INT J ENERG RES, V22, P791, DOI 10.1002/(SICI)1099-114X(199807)22:9<791::AID-ER393>3.0.CO
[4]  
2-W
[5]   Working fluids for an absorption system based on R124 (2-chloro-1,1,1,2-tetrafluoroethane) and organic absorbents [J].
Borde, I ;
Jelinek, M ;
Daltrophe, NC .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1997, 20 (04) :256-266
[6]   Purification of seawater using absorption heat transformers with water-(LiBr+-LiI+LNO3+LiCl) and low temperature heat sources [J].
Bourouis, A ;
Coronas, A ;
Romero, RJ ;
Siqueiros, J .
DESALINATION, 2004, 166 (1-3) :209-214
[7]   Industrial waste heat recovery technologies: An economic analysis of heat transformation technologies [J].
Brueckner, Sarah ;
Liu, Selina ;
Miro, Laia ;
Radspieler, Michael ;
Cabeza, Luisa F. ;
Laevemanna, Eberhard .
APPLIED ENERGY, 2015, 151 :157-167
[8]  
Centre IHP, 2014, IEA HEAT PUMP PROGR, V35
[9]   Integration of absorption heat pumps in a Kraft pulp process for enhanced energy efficiency [J].
Costa, Andrea ;
Bakhtiari, Bahador ;
Schuster, Sebastian ;
Paris, Jean .
ENERGY, 2009, 34 (03) :254-260
[10]   First and second law multidimensional analysis of a triple absorption heat transformer (TAHT) [J].
Donnellan, Philip ;
Byrne, Edmond ;
Oliveira, Jorge ;
Cronin, Kevin .
APPLIED ENERGY, 2014, 113 :141-151