A low-voltage ride-through capability enhancement scheme of doubly fed induction generator based wind plant considering grid faults

被引:13
作者
Gayen, P. K. [1 ]
Chatterjee, D. [2 ]
Goswami, S. K. [2 ]
机构
[1] Kalyani Govt Engn Coll, Dept Elect Engn, Kalyani 741235, Nadia, India
[2] Jadavpur Univ, Dept Elect Engn, Kolkata 700032, India
关键词
SHORT-CIRCUIT CURRENT; CONTROL STRATEGY; DYNAMIC-BEHAVIOR; TURBINES; SYSTEMS; DIPS; PENETRATION; CROWBAR; SPEED;
D O I
10.1063/1.4943121
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper presents an improved low-voltage ride-through (LVRT) capability scheme of a grid connected doubly fed induction generator (DFIG) during any type of grid fault. In this context, an effective switching strategy based on computation of rotor current components has been suggested for the proposed passive protection circuits of a rotor side converter (RSC). Simultaneously, the RSC will control the fundamental rotor current within its available capacity for providing reactive power to the faulty grid. The proposed passive protection circuits comprise both stator and rotor side series resistor based passive compensators. The stator passive compensator will only be operated at starting and ending instant of fault to restrict rotor inrush current regardless of the type of fault. On the other hand, the rotor passive compensator is conditionally activated at the time of unbalanced fault to keep the overall rotor current under control. During both types of fault, RSC performs dual functions as partially scaled active compensator cum fractional reactive power generation controlling element. Thus, coordinated operation of passive compensator(s) and RSC will improve the LVRT ability of DFIG based wind power plants under any fault scenario. Various simulations are performed on 1.5MW DFIG to show the advantage of this proposed control strategy. (C) 2016 AIP Publishing LLC.
引用
收藏
页数:19
相关论文
共 47 条
[1]   Coordinated reactive power management in power networks with wind turbines and FACTS devices [J].
Amaris, Hortensia ;
Alonso, Monica .
ENERGY CONVERSION AND MANAGEMENT, 2011, 52 (07) :2575-2586
[2]   Direct model reference adaptive internal model controller for better voltage sag ride through in doubly fed induction generator wind farms [J].
Amuthan, N. ;
Subburaj, P. ;
Mary, P. Melba .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 47 :255-263
[3]  
[Anonymous], 2014, Grid Integration of Wind Energy
[4]  
Bollen M.H., 1999, UNDERSTANDING POWER
[5]   Experimental evaluation of wind turbines maximum power point tracking controllers [J].
Camblong, H. ;
de Alegria, I. Martinez ;
Rodriguez, M. ;
Abad, G. .
ENERGY CONVERSION AND MANAGEMENT, 2006, 47 (18-19) :2846-2858
[6]   Fault ride-through capability of DFIG wind turbines [J].
Hansen, Anca D. ;
Michalke, Gabriele .
RENEWABLE ENERGY, 2007, 32 (09) :1594-1610
[7]   Control Strategies for Augmenting LVRT Capability of DFIGs in Interconnected Power Systems [J].
Hossain, M. Jahangir ;
Saha, Tapan Kumar ;
Mithulananthan, Nadarajah ;
Pota, Hemanshu R. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2013, 60 (06) :2510-2522
[8]   An Improved Low-Voltage Ride-Through Control Strategy of Doubly Fed Induction Generator During Grid Faults [J].
Hu, Sheng ;
Lin, Xinchun ;
Kang, Yong ;
Zou, Xudong .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2011, 26 (12) :3653-3665
[9]   A comprehensive review on the grid integration of doubly fed induction generator [J].
Jadhav, H. T. ;
Roy, Ranjit .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 49 :8-18
[10]   Feedforward Transient Compensation Control for DFIG Wind Turbines During Both Balanced and Unbalanced Grid Disturbances [J].
Liang, Jiaqi ;
Howard, Dustin F. ;
Restrepo, Jose A. ;
Harley, Ronald G. .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2013, 49 (03) :1452-1463