A Case Study on 500 kV Line Performance Related to Lightning in Malaysia

被引:15
|
作者
Rawi, Iryani Mohamed [1 ,2 ]
Ab Kadir, Mohd Zainal Abidin [3 ]
Gomes, Chandima [3 ]
Azis, Norhafiz [3 ]
机构
[1] Tenaga Nas Berhad, Engn Dept, TNB Transmiss Div, Kuala Lumpur 50470, Malaysia
[2] Univ Putra Malaysia, Serdang 43400, Malaysia
[3] Univ Putra Malaysia, Fac Engn, Serdang 43400, Malaysia
关键词
Ground flash density (GFD); lightning detection network (LDN); lightning; monsoon; overhead lines; statistics; tower footing resistance (TFR); VOLTAGE TRANSMISSION-LINES; OUTAGES;
D O I
10.1109/TPWRD.2017.2787660
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Lightning-related outages are of great concern for power utility companies especially in the tropical regions. Tenaga Nasional Berhad as the system operator in Malaysia realized the importance of this issue. In this paper, statistical information on transmission line outages, together with lightning stroke data, are presented. Lightning data were obtained from TNB Lightning Detection Network which generates lightning density map and other information, such as peak current, polarity, and location of the detected strokes with 500-m location accuracy. A case study on the 500 kV A-to-B line represents statistical information of collected strokes where 18 kA and 14 kA were reported as median values of current peak for negative and positive strokes, respectively. Mean values are 22 kA for negative strokes and 17 kA for positive strokes. About 93% of 658 619 collected strokes from 2004 to 2015 are negative whereas the remaining are positive. A total of 582 (90%) negative strokes and 65 (10%) positive strokes were recorded along a selected case line where 83% of outages were reported to occur on the top phase. Lightning stroke density, terrain characteristics, tower footing resistance, and monsoon activities were highlighted as contributing factors on line performance due to lightning in this study.
引用
收藏
页码:2180 / 2186
页数:7
相关论文
共 50 条
  • [1] Lightning study and experience on the first 500kV Transmission Line Arrester in Malaysia
    Rawi, Iryani Mohamed
    Ab Kadir, M. Z. A.
    Azis, Norhafiz
    2014 INTERNATIONAL CONFERENCE ON LIGHTNING PROTECTION (ICLP), 2014, : 1106 - 1109
  • [2] Application of GRNN to study of the lightning shielding performance for 500 kV transmission line
    School of Electrical Engineering, Wuhan University, Wuhan 430072, China
    Gaodianya Jishu, 2006, 5 (26-30):
  • [3] Case Study of the Lightning Performance of a 230 kV Transmission Line
    Humayun, Muhammad
    Schoene, Jens
    Mueller, Dave
    Pallem, Chandra
    2018 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION (T&D), 2018,
  • [4] Corona lightning overvoltage analysis for a 500 kV hybrid line
    Said, Abdelrahman
    Anane, Zahira
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (04) : 532 - 541
  • [5] Study on lightning performance for ±500 kV DC double circuit transmission lines
    Nie, Dingzhen
    Zhou, Peihong
    Dai, Min
    Wang, Dongmei
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (01): : 148 - 151
  • [6] Study on calculation model of the lightning protection performance of shielding failure for 500kV double circuit transmission line
    Zhang, ZJ
    Sima, WX
    Liao, RJ
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2003, : 122 - 124
  • [7] Analysis on lightning withstand performance of the Sanhu ±500 kV double circuit HVDC power transmission line
    Tan, Jin
    Zhang, Huan-Qing
    Liu, Yu-Jun
    Liang, Jian
    Tang, Cheng
    Liu, Gang
    Gaodianya Jishu/High Voltage Engineering, 2010, 36 (09): : 2173 - 2179
  • [8] Assessment on lightning performance of ±500 kV overhead DC power transmission line from Yichang to Shanghai
    Yue, Lingping
    Lu, Liping
    Zhang, Xuyong
    Dai, Jianhua
    Dianwang Jishu/Power System Technology, 2012, 36 (07): : 161 - 165
  • [9] Effect of Line Voltage on Lightning Attachment to 220-kV and 500-kV Lines
    Podporkin, Georgy
    2017 INTERNATIONAL SYMPOSIUM ON LIGHTNING PROTECTION (XIV SIPDA), 2017, : 7 - 13
  • [10] Study on Lightning Resistance Level of 500 kV Single Circuit AC Transmission Line Considering Subsequent Lightning Return Stroke
    Du Z.
    He J.
    Liu S.
    Yue G.
    Gan Y.
    Cai H.
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2023, 50 (02): : 157 - 164