Dynamic operational characteristics and preliminary control of a packed liquid desiccant dehumidifier

被引:5
作者
Zhang, Xiaobo [2 ]
Zhu, Yuxian [2 ]
Xu, Xiangguo [1 ,2 ]
Ji, Xiaosheng [3 ]
机构
[1] Zhejiang Univ, Ctr Balance Architecture, 38 Zheda Rd, Hangzhou 310027, Peoples R China
[2] Zhejiang Univ, Key Lab Refrigerat & Cryogen Technol Zhejiang Pro, Inst Refrigerat & Cryogen, 38 Zheda Rd, Hangzhou 310027, Peoples R China
[3] Chinese Acad Sci, Sanya Inst Oceanol, Sanya 572000, Hainan, Peoples R China
关键词
Dynamic characteristics; Control performance; Liquid desiccant; Packed dehumidifier; MASS-TRANSFER; AIR; HEAT;
D O I
10.1016/j.enbuild.2021.111185
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Liquid desiccant dehumidifiers (LDDs) has attracted much attention due to its advantages of energy saving and environmental protection. However, dynamic characteristics of LDDs, which are essential to develop appropriate control methods, are still not clear at present. In this paper, the performance of a packed LDD was investigated under changes of desiccant inlet temperature and flow rate as well as air inlet humidity ratio, temperature and flow rate. Due to the random packings and interaction between air and desiccant, the air is normally distributed randomly during a dynamic process of LDDs and air outlet humidity ratio at the sampling point is serrated with time going. It was found that exponent function could be utilized to smooth the experimental result of air outlet humidity ratio, providing a simple way to determine the evaluation indexes like the response delay and response time as well as response rate, which could facilitate to evaluate dynamic characteristics of the dehumidifier. And through comparing those evaluation indexes corresponding to changes of different inlet parameters, it was revealed that air outlet humidity ratio was more sensitive to the change of desiccant or air flow rate, but not desiccant inlet temperature as indicated in a previous research getting from quasi-steady state experiments. Therefore, it would be more reasonable to select the desiccant or air flow rate as control variables instead of desiccant inlet temperature. Furthermore, preliminary control experiments were conducted to compare the performance of control algorithms developed based on the steady state characteristics and expert experience of dynamic characteristics. Results show that the control algorithm developed based on the expert experience of dynamic characteristics performs much better, which indicates that the obtained steady state characteristics in existing researches are unsuitable for developing control algorithms for a packed LDD. The dynamic characteristics revealed in current research paves the way for the future development of appropriate control algorithms. (c) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:9
相关论文
共 50 条
  • [21] Liquid desiccant dehumidifier: Development of a new performance predication model based on CFD
    Luo, Yimo
    Yang, Hongxing
    Lu, Lin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 69 : 408 - 416
  • [22] Natural induced flow due to concentration gradient in a liquid desiccant air dehumidifier
    Fazilati, Mohammad Ali
    Sedaghat, Ahmad
    Alemrajabi, Ali Akbar
    APPLIED THERMAL ENGINEERING, 2016, 105 : 105 - 117
  • [23] Dynamic and microscopic simulation of the counter-current flow in a liquid desiccant dehumidifier
    Luo, Yimo
    Yang, Hongxing
    Lu, Lin
    APPLIED ENERGY, 2014, 136 : 1018 - 1025
  • [24] Analysis on the Significance of Effects from Operational Conditions on the Performances of Ultrasonic Atomization Dehumidifier with Liquid Desiccant
    Yang, Zili
    Zhang, Kaisheng
    Lian, Zhiwei
    9TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING (ISHVAC) JOINT WITH THE 3RD INTERNATIONAL CONFERENCE ON BUILDING ENERGY AND ENVIRONMENT (COBEE), 2015, 121 : 89 - 94
  • [25] Experimental analysis of an internally-cooled liquid desiccant dehumidifier
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Jingjing
    Chang, Xiaoming
    Jiang, Yi
    BUILDING AND ENVIRONMENT, 2013, 63 : 1 - 10
  • [26] An experimental study of structured packing dehumidifier/regenerator operating with liquid desiccant
    Bassuoni, M. M.
    ENERGY, 2011, 36 (05) : 2628 - 2638
  • [27] Computational analysis of spray type counter flow liquid desiccant dehumidifier
    Ahmed, M. Ijas
    Vignesh, R.
    Kumar, L. Gangadhara Kiran
    MATERIALS TODAY-PROCEEDINGS, 2021, 46 : 9820 - 9826
  • [28] Performance characteristics assessment of hollow fiber membrane-based liquid desiccant dehumidifier for drying application
    Tejes, P. K. S.
    Priyadarshi, Gaurav
    Naik, B. Kiran
    APPLIED THERMAL ENGINEERING, 2023, 218
  • [29] An experimental study on the dehumidification performance of a counter flow liquid desiccant dehumidifier
    Wang, Lingshi
    Xiao, Fu
    Zhang, Xuejun
    Kumar, Ritunesh
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 70 : 289 - 301
  • [30] Investigations of a Dehumidifier in a Solar-Assisted Liquid Desiccant Demonstration Plant
    Jaradat, Mustafa
    Fleig, Daniel
    Vajen, Klaus
    Jordan, Ulrike
    JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2019, 141 (03):