Droop Control of Converter-Interfaced Microsources in Rural Distributed Generation

被引:164
作者
Majumder, Ritwik [1 ]
Ledwich, Gerard [1 ]
Ghosh, Arindam [1 ]
Chakrabarti, Saikat [1 ]
Zare, Firuz [1 ]
机构
[1] Queensland Univ Technol, Sch Engn Syst, Brisbane, Qld 4001, Australia
关键词
Active and reactive power sharing; angle droop; autonomous microgrid; resistive lines;
D O I
10.1109/TPWRD.2010.2042974
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes new droop control methods for load sharing in a rural area with distributed generation. Highly resistive lines, typical of rural low voltage networks, always create a big challenge for conventional droop control. To overcome the conflict between higher feedback gain for better power sharing and system stability in angle droop, two control methods have been proposed. The first method considers no communication among the distributed generators (DGs) and regulates the converter output voltage and angle ensuring proper sharing of load in a system having strong coupling between real and reactive power due to high line resistance. The second method, based on a smattering of communication, modifies the reference output voltage angle of the DGs depending on the active and reactive power flow in the lines connected to point of common coupling (PCC). It is shown that with the second proposed control method, an economical and minimum communication system can achieve significant improvement in load sharing. The difference in error margin between proposed control schemes and a more costly high bandwidth communication system is small and the later may not be justified considering the increase in cost. The proposed control shows stable operation of the system for a range of operating conditions while ensuring satisfactory load sharing.
引用
收藏
页码:2768 / 2778
页数:11
相关论文
共 16 条
[1]   Evaluation of configuration plans for DGs in developing countries using advanced planning techniques [J].
Agalgaonkar, AP ;
Kulkarni, SV ;
Khaparde, SA .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2006, 21 (02) :973-981
[2]  
[Anonymous], IEEE T POWER ELECT
[3]  
[Anonymous], KLUWERS POWER ELECT
[4]  
*AUSTR BUS COUNC S, 2010, CLEAN EN COUNC AB IN
[5]  
Blyden, 2006, P POW ENG SOC GEN M, P1, DOI 10.1109/PES.2006.1709540
[6]   CONTROL OF PARALLEL CONNECTED INVERTERS IN STANDALONE AC SUPPLY-SYSTEMS [J].
CHANDORKAR, MC ;
DIVAN, DM ;
ADAPA, R .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1993, 29 (01) :136-143
[7]   A new approach to load balancing and power factor correction in power distribution system [J].
Ghosh, A ;
Joshi, A .
IEEE TRANSACTIONS ON POWER DELIVERY, 2000, 15 (01) :417-422
[8]  
Kundur P., 1993, Power System Stability And Control
[9]   A security mechanism of web services-based communication for wind power plants [J].
Liu, Nian ;
Zhang, Jianhua ;
Liu, Wenxia .
IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (04) :1930-1938
[10]   Load sharing and power quality enhanced operation of a distributed microgrid [J].
Majumder, R. ;
Ghosh, A. ;
Ledwich, G. ;
Zare, F. .
IET RENEWABLE POWER GENERATION, 2009, 3 (02) :109-119