A study of estimation techniques for frequency-relaying applications

被引:4
作者
ElHawary, ME [1 ]
Mostafa, MA [1 ]
ElArabaty, AM [1 ]
Mansour, MM [1 ]
ElNaggar, KM [1 ]
机构
[1] AIN SHAMS UNIV,CAIRO,EGYPT
来源
CANADIAN JOURNAL OF ELECTRICAL AND COMPUTER ENGINEERING-REVUE CANADIENNE DE GENIE ELECTRIQUE ET INFORMATIQUE | 1996年 / 21卷 / 01期
关键词
D O I
10.1109/CJECE.1996.7102112
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
This paper presents an evaluation and performance comparison of two estimating algorithms used for frequency-relaying applications. The first algorithm is based on least squares (LS) error estimation, while the second is based on the least absolute value (LAV) approximations. Two models for frequency estimation, namely the constant-frequency model (CFM) and the variable-frequency model (VFM), are used. CFM is used to measure the steady-state frequency deviation, while VFM is used to measure the transient frequency and its rate of change. For the constant-frequency model, which is suitable for use in microprocessor-based relays, the algorithms are tested using two data sets. The first involves a pure sine waveform, and the second is a wave generated from the electromagnetic transients program (EMTP) simulating a study system. The EMTP is used to generate the corresponding voltage samples at a relay location. Fault conditions applied on the study system to generate distorted waves with and without frequency deviations are considered. For the variable-frequency model, the algorithms are tested using a data set generated from a pure sine waveform. The effects of sampling rate, sample window size and bad data on the performance of each algorithm are studied. A comparison of the results is offered to evaluate the two techniques.
引用
收藏
页码:9 / 20
页数:12
相关论文
共 16 条
  • [1] Bauman H.A., 1955, AIEE T POWER APPARAT, VPAS-74, P1632
  • [2] AN ADAPTIVE SAMPLING-INTERVAL GENERATOR FOR DIGITAL RELAYING
    BENMOUYAL, G
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) : 1602 - 1609
  • [3] BERRY DH, 1970, CIGRE INT C
  • [4] PHASE-ANGLE MEASUREMENTS WITH SYNCHRONIZED CLOCKS - PRINCIPLE AND APPLICATIONS
    BONANOMI, P
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (12): : 5036 - 5043
  • [5] Christensen G. S., 1989, Canadian Journal of Electrical and Computer Engineering, V14, P24
  • [6] OFF-NOMINAL FREQUENCY MEASUREMENTS IN ELECTRIC-POWER SYSTEMS
    GIRAY, MM
    SACHDEV, MS
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1989, 4 (03) : 1573 - 1579
  • [7] A NEW FFT-BASED DIGITAL FREQUENCY RELAY FOR LOAD SHEDDING
    GIRGIS, AA
    HAM, FM
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1982, 101 (02): : 433 - 439
  • [8] GUNTHER E, 1993, IEEE COMPUTER AP JAN, P33
  • [9] NEW DIGITAL SIGNAL-PROCESSING ALGORITHMS FOR FREQUENCY DEVIATION MEASUREMENT
    KEZUNOVIC, M
    SPASOJEVIC, P
    PERUNICIC, B
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1992, 7 (03) : 1563 - 1573
  • [10] EMTP - A powerful tool for analyzing power system transients
    Long, Willis
    Cotcher, David
    Ruiu, Dan
    Adam, Philippe
    Lee, Sang
    Adapa, Rambabu
    [J]. IEEE Computer Applications in Power, 1990, 3 (03): : 36 - 41