An Adaptive Autoreclosure Scheme with Reference to Transient Stability for Transmission Lines

被引:9
作者
Heo, Jeong-Yong [1 ]
Oh, Yun-Sik [1 ]
Seo, Hun-Chul [2 ]
Kim, Chul-Hwan [1 ]
机构
[1] Sungkyunkwan Univ, Coll Informat & Commun Engn, Seoul, South Korea
[2] Yonam Inst Digital Technol, Sch IT Engn, Jinju Si, Gyeongsangnam D, South Korea
基金
新加坡国家研究基金会;
关键词
Autoreclosure; Adaptive reclosure; Optimal reclosing time; Phase-by-phase reclosure; Transient stability EMTP; REAL-TIME; RECLOSURE; SYSTEMS;
D O I
10.5370/JEET.2015.10.3.795
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Autoreclosure provides a means of improving power transmitting ability and system stability. Conventional reclosure adopts the fixed dead time interval strategy, where the reclosure is activated after a time delay to restore the system to normal as quickly as possible without regard to the system conditions. However, these simple techniques cannot provide optimal operating performance. This paper presents an adaptive autoreclosure algorithm including variable dead time, optimal reclosure, phase-by-phase reclosure and emergency extended equal-area criterion (EEEAC) algorithm in order to improve system stability. The reclosure algorithm performs the operations that are attuned to the power system conditions. The proposed adaptive reclosure algorithm is verified and tested using ATP/EMTP MODELS, and the simulation results show that the system oscillations are reduced and the transient stability is enhanced by employing the proposed adaptive reclosure algorithm.
引用
收藏
页码:795 / 803
页数:9
相关论文
共 17 条
[11]   PREDICTING FUTURE BEHAVIOR OF TRANSIENT EVENTS RAPIDLY ENOUGH TO EVALUATE REMEDIAL CONTROL OPTIONS IN REAL-TIME [J].
ROVNYAK, S ;
LIU, CW ;
LU, J ;
MA, WM ;
THORP, J .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1995, 10 (03) :1195-1203
[12]   Analysis of Magnitude and Rate-of-rise of VFTO in 550 kV GIS using EMTP-RV [J].
Seo, Hun-Chul ;
Jang, Won-Hyeok ;
Kim, Chul-Hwan ;
Chung, Young-Hwan ;
Lee, Dong-Su ;
Rhee, Sang-Bong .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2013, 8 (01) :11-19
[13]   A new method for power system transient instability detection [J].
Wang, LC ;
Girgis, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (03) :1082-1089
[14]   A SIMPLE DIRECT METHOD FOR FAST TRANSIENT STABILITY ASSESSMENT OF LARGE POWER-SYSTEMS [J].
XUE, Y ;
CUTSEM, TV ;
RIBBENSPAVELLA, M .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1988, 3 (02) :400-412
[15]   Analysis of Transient Overvoltages within a 345kV Korean Thermal Plant [J].
Yeo, Sang-Min ;
Kim, Chul-Hwan .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2012, 7 (03) :297-303
[16]  
Yuan Y. C., 1998, P 1998 POWERCON C AU, P18
[17]   Computation of optimal reclosure time for transmission lines [J].
Zhang, BHH ;
Yuan, YCC ;
Chen, Z ;
Bo, ZQQ .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2002, 17 (03) :670-675