Thermal behaviour of interactive mechanically ventilated double glazed facade: Non-dimensional analysis

被引:34
作者
Balocco, C
Colombari, M
机构
[1] Univ Florence, Dipartimento Energet, I-50139 Florence, Italy
[2] Permasteelisa, Res & Engn, I-31100 Vendemiano, TV, Italy
关键词
non-dimensional analysis; double-skin facade; mechanical ventilation; monitoring test results; heat transfer;
D O I
10.1016/j.enbuild.2005.02.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Non-dimensional analysis is proposed as a method to analyse mechanically ventilated double glazed facade energy performance. The 12 non-dimensional numbers defined, can be used to describe thermal and energy performance of interactive facade designs. A comparison between Nusselt number solved by experimental data and Nusselt calculated by the validated multivariable correlation function is reported in the present paper. Due to its wide validity field the proposed method can be used to analyze thermodynamic performances of glass double-skin facades with mechanical ventilation. Applying it, useful design indications can be derived also by varying some parameters using thermo-physical and climatic data easy to get. (c) 2005 Elsevier B.V. All rights reserved.
引用
收藏
页码:1 / 7
页数:7
相关论文
共 21 条
[1]  
Bevington, 1969, DATA REDUCTION ERROR
[2]   Ventilated facades energy performance in summer cooling of buildings [J].
Ciampi, M ;
Leccese, F ;
Tuoni, G .
SOLAR ENERGY, 2003, 75 (06) :491-502
[3]  
COLOMBARI M, 2001, P 6 WORLD C COUNC TA
[4]  
COLOMBARI M, 2002, EPIC 2002 AIVC 3 C E
[5]  
COLOMBARI M, 2002, INDOOR AIR 2002
[6]  
COLOMBARI M, 2003, 54 C ATI ASS TERM IT
[7]   Simulation and control of ventilation rates in greenhouses [J].
Dayan, J ;
Dayan, E ;
Strassberg, Y ;
Presnov, E .
MATHEMATICS AND COMPUTERS IN SIMULATION, 2004, 65 (1-2) :3-17
[8]   Numerical analysis of the thermal behaviour of glazed ventilated facades in Mediterranean climates. Part II: applications and analysis of results [J].
Faggembauu, D ;
Costa, M ;
Soria, M ;
Oliva, A .
SOLAR ENERGY, 2003, 75 (03) :229-239
[9]   Numerical analysis of the thermal behaviour of ventilated glazed facades in Mediterranean climates. Part I: development and validation of a numerical model [J].
Faggembauu, D ;
Costa, M ;
Soria, M ;
Oliva, A .
SOLAR ENERGY, 2003, 75 (03) :217-228
[10]   Natural cooling strategies efficiency in an office building with a double-skin facade [J].
Gratia, E ;
De Herde, A .
ENERGY AND BUILDINGS, 2004, 36 (11) :1139-1152