Enhancing the cooling and dehumidification performance of indirect evaporative cooler by hydrophobic-coated primary air channels

被引:16
作者
Min, Yunran [1 ]
Shi, Wenchao [1 ]
Shen, Boxu [1 ]
Chen, Yi [2 ]
Yang, Hongxing [1 ]
机构
[1] Hong Kong Polytech Univ, Res Inst Smart Energy RISE, Renewable Energy Res Grp RERG, Hong Kong, Peoples R China
[2] Jimei Univ, Sch Mech & Energy Engn, Fujian, Peoples R China
关键词
Indirect evaporative cooler; Condensation; Heat transfer; Hydrophobic surface; CONDENSATION HEAT-TRANSFER; MAISOTSENKO CYCLE HEAT; CROSS-FLOW; COUNTER; EXCHANGER; RECOVERY; CONFIGURATION; SYSTEMS; MODEL;
D O I
10.1016/j.ijheatmasstransfer.2021.121733
中图分类号
O414.1 [热力学];
学科分类号
摘要
An indirect Evaporative Cooler (IEC) for air-conditioning (AC) energy recovery is a rapidly developing technology and has great potential applications in hot and humid regions. As the cooling potential of exhaust air is captured to evaporate the spraying water, the humid fresh air in adjacent channels can be cooled with moisture extracted. The condensation of fresh air can pose significant influences on the cooling and dehumidification performance of the cooler. However, the effect of surface modification on both sensible and latent heat transfer in dry channels of IEC was hardly discussed in the literature. In this paper, a novel IEC heat exchanger was proposed by depositing the hydrophobic nanoparticles on the sur-faces of primary air channels. Visualized experiments were carried out to compare the condensation heat transfer mechanisms as well as the effects of influence factors on the performance of the hydrophobic-coated IEC and the traditional un-coated one. Results show that, larger irregular droplets drained off as water film was observed on the bare-aluminum plate, while the hydrophobic surface promoted drop-wise condensation with a smaller droplet diameter. The minimized size of falling-off droplets and fre-quent droplet removal can enhance the convective heat transfer of the processed air flowing over the coated plate surface. The hydrophobic coating treatment on the primary air channel surfaces increased the energy-saving rate of IEC by 8.5-17.2%, which can potentially be utilized in AC applications under dehumidifying conditions. (c) 2021 Elsevier Ltd. All rights reserved.
引用
收藏
页数:13
相关论文
共 40 条
  • [1] Experimental study on condensation heat transfer of steam on vertical titanium plates with different surface energies
    Baojin, Qi
    Li, Zhang
    Hong, Xu
    Yan, Sun
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2011, 35 (01) : 211 - 218
  • [2] Parameter sensitivity analysis and configuration optimization of indirect evaporative cooler (IEC) considering condensation
    Chen, Yi
    Yang, Hongxing
    Luo, Yimo
    [J]. APPLIED ENERGY, 2017, 194 : 440 - 453
  • [3] A simplified analytical model for indirect evaporative cooling considering condensation from fresh air: Development and application
    Chen, Yi
    Luo, Yimo
    Yang, Hongxing
    [J]. ENERGY AND BUILDINGS, 2015, 108 : 387 - 400
  • [4] Coleman H.W., 2018, J ENG IND, V4th
  • [5] Performance evaluation of an indirect pre-cooling evaporative heat exchanger operating in hot and humid climate
    Cui, X.
    Chua, K. J.
    Islam, M. R.
    Ng, K. C.
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2015, 102 : 140 - 150
  • [6] Effect of heat exchanger plates geometry on performance of an indirect evaporative cooling system
    De Antonellis, Stefano
    Cignatta, Luca
    Facchini, Chiara
    Liberati, Paolo
    [J]. APPLIED THERMAL ENGINEERING, 2020, 173 (173)
  • [7] Experimental study on dehumidification performance enhancement by TiO2 superhydrophilic coating for liquid desiccant plate dehumidifiers
    Dong, Chuanshuai
    Lu, Lin
    Wen, Tao
    [J]. BUILDING AND ENVIRONMENT, 2017, 124 : 219 - 231
  • [8] A model for condensate retention on plain-fin heat exchangers
    ElSherbini, A. I.
    Jacobi, A. M.
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2006, 128 (05): : 427 - 433
  • [9] Effect of plates coating on performance of an indirect evaporative cooling system
    Guilizzoni, Manfredo
    Milani, Samanta
    Liberati, Paolo
    De Antonellis, Stefano
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 367 - 375
  • [10] Heat transfer and pressure drop characteristics of wet air flow in metal foam with hydrophobic coating under dehumidifying conditions
    Hu, Haitao
    Lai, Zhancheng
    Ding, Guoliang
    [J]. APPLIED THERMAL ENGINEERING, 2018, 132 : 651 - 664