Estimation of Paper Moisture Content based on Dielectric Dissipation Factor of Oil-paper Insulation under Non-sinusoidal Excitations

被引:37
作者
Pradhan, A. K. [1 ]
Chatterjee, B. [1 ]
Chakravorti, S. [1 ]
机构
[1] Jadavpur Univ, Dept Elect Engn, Kolkata, India
关键词
Sinusoidal and non-sinusoidal excitation; dielectric dissipation factor; harmonic components; oil-paper insulation; paper moisture; condition monitoring; FREQUENCY-DOMAIN; POLARIZATION; SPECTROSCOPY; TIME;
D O I
10.1109/TDEI.2015.7076781
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency Domain Spectroscopy is a popular non-invasive method that is widely used for condition assessment of oil-paper insulation in real-life power transformers. Conventional Frequency Domain Spectroscopy is done using sinusoidal excitation over a wide frequency range. In this work, a different approach has been taken to investigate some more possibilities of Frequency Domain Spectroscopy using non-sinusoidal excitation for a better condition assessment of oil-paper insulation. For that, triangular waveshape was chosen as non-sinusoidal excitations whose slope can be changed to vary the harmonic content and amplitudes of constituent components. Samples with preset moisture contents that emulate the oil-paper insulation of real-life transformer have been prepared in the laboratory for the assessment of insulation condition. For a comparative study, both sinusoidal and triangular excitations having same peak as well as time period are applied to the prepared samples under controlled environmental condition and corresponding dielectric response currents are measured. From the applied voltages and corresponding dielectric response currents, dielectric dissipation factors are calculated and compared. It has been observed that use of non-sinusoidal excitation provides better results than sinusoidal excitation in the estimation of paper moisture content. It has also been observed that among the applied non-sinusoidal excitations, a particular waveform provides more accurate information about the paper moisture content.
引用
收藏
页码:822 / 830
页数:9
相关论文
共 33 条
[1]  
[Anonymous], 2010, MAT ENG SCI PROCESSI
[2]  
Ashby M.F., 2006, Engineering Materials 1: An Introduction to Properties, Applications and Design
[3]  
Ashby M.F., 2005, ENG MAT, V3rd
[4]  
Askeland DonaldR., 2006, The Science Engineering of Mate- rials
[5]   Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics [J].
Blennow, J ;
Ekanayake, C ;
Walczak, K ;
García, B ;
Gubanski, SM .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :681-688
[6]  
Budinski K.G., 2009, Engineering Materials: Properties and Selection
[7]  
Callister W.D., 2007, FUNDAMENTALS MAT SCI
[8]  
Callister W.D. J., 2010, MAT SCI ENG INTRO, P46
[9]  
*CIGR TASK FORC, 2002, ELECTRA, P25
[10]   Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation [J].
Ekanayake, Chandima ;
Gubanski, Stanislaw M. ;
Graczkowski, Andrzej ;
Walczak, Krzysztof .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) :1309-1317