Nondetection Index of Anti-Islanding Passive Protection of Synchronous Distributed Generators

被引:14
作者
Salles, Diogo [1 ]
Freitas, Walmir [1 ]
Vieira, Jose C. M. [2 ]
Xu, Wilsun [3 ]
机构
[1] Univ Estadual Campinas, Dept Elect Energy Syst, BR-13083852 Campinas, SP, Brazil
[2] Univ Sao Paulo, Sao Carlos Sch Engn, BR-13566590 Sao Carlos, SP, Brazil
[3] Univ Alberta, Dept Elect & Comp Engn, Edmonton, AB T6G 2V4, Canada
基金
巴西圣保罗研究基金会;
关键词
Distributed generation; distribution system; islanding; nondetection zone; synchronous generator; RELAYS; PERFORMANCE; SYSTEMS;
D O I
10.1109/TPWRD.2012.2190624
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Synchronous distributed generators are prone to operate islanded after contingencies, which is usually not allowed due to safety and power-quality issues. Thus, there are several anti-islanding techniques; however, most of them present technical limitations so that they are likely to fail in certain situations. Therefore, it is important to quantify and determine whether the scheme under study is adequate or not. In this context, this paper proposes an index to evaluate the effectiveness of anti-islanding frequency-based relays commonly used to protect synchronous distributed generators. The method is based on the calculation of a numerical index that indicates the time period that the system is unprotected against islanding considering the global period of analysis. Although this index can precisely be calculated based on several electromagnetic transient simulations, a practical method is also proposed to calculate it directly from simple analytical formulas or lookup tables. The results have shown that the proposed approach can assist distribution engineers to assess and set anti-islanding protection schemes.
引用
收藏
页码:1509 / 1518
页数:10
相关论文
共 25 条
  • [1] [Anonymous], 2009, DISTR GEN TECHN INT
  • [2] [Anonymous], 2003, G751 EL ASS STAND
  • [3] [Anonymous], 2003, P1547 IEEE
  • [4] [Anonymous], 2011, 12412010 IEEE, DOI DOI 10.1109/IEEESTD.2011.5960751
  • [5] Brundlinger R., 2005, IEEE POWERTECH ST PE
  • [6] CIGRE Working Group 37.23, 1999, 3723 CIGRE WORK GROU
  • [7] Cullen N., 2002, T508 IEA PVPS
  • [8] Investigation of the Local Passive Anti-Islanding Scheme in a Distribution System Embedding a PMSG-Based Wind Farm
    El-Khattam, Walid
    Yazdani, Amirnaser
    Sidhu, Tarlochan S.
    Seethapathy, Ravi
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) : 42 - 52
  • [9] Energy Networks Assoc, 2008, G8311 EN NETW ASS
  • [10] A practical method for assessing the effectiveness of vector surge relays for distributed generation applications
    Freitas, W
    Huang, ZY
    Xu, WS
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (01) : 57 - 63