Line-interactive UPS using a fuel cell as the primary source

被引:183
作者
Tao, Haimin [1 ,2 ]
Duarte, Jorge L. [2 ,3 ]
Hendrix, Marcel A. M. [1 ,2 ]
机构
[1] Philips Lighting BV, NL-5611 BD Eindhoven, Netherlands
[2] Eindhoven Univ Technol, Dept Elect Engn, Electromech & Power Elect Grp, NL-5600 MB Eindhoven, Netherlands
[3] Philips Power Solut, NL-5652 AM Eindhoven, Netherlands
关键词
active filters; fuel cells; supercapacitors; uninterruptible power systems;
D O I
10.1109/TIE.2008.918472
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
This paper proposes a line-interactive fuel-cell-powered uninterruptible-power-supply system. A three-port bidirectional converter connects a fuel cell and a supercapacitor to a grid-interfacing inverter. The system can operate in both stand-alone and grid-connected modes. Moreover, an active filtering function is integrated into the system. It is shown that a supercapacitor can serve as both an active and a reactive energy storage and can buffer the periodical low-frequency ripple in the requested power. For connecting the system to the utility grid, a high-performance single-phase phase-locked loop that incorporates an orthogonal filter is presented. Resonant controllers for both the voltage and current regulations eliminate steady-state error and implement selective harmonic compensation. Simulation and experimental results are provided to show the feasibility of the proposed system and the effectiveness of the control methods.
引用
收藏
页码:3012 / 3021
页数:10
相关论文
共 25 条
[1]  
[Anonymous], P IEEE OC 2007 AB
[2]   Control strategy for grid-connected DC-AC converters with load power factor correction [J].
Barbosa, PG ;
Rolim, LGB ;
Watanabe, EH ;
Hanitsch, R .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1998, 145 (05) :487-491
[3]  
Benhabib MC, 2005, EPE J, V15, P36
[4]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[5]   A three-phase UPS that complies with the standard IEC 62040-3 [J].
Botteron, Fernando ;
Pinheiro, Humberto .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (04) :2120-2136
[6]  
Choi W, 2003, IEEE POWER ELECTRON, P385
[7]   An electrochemical-based fuel-cell model suitable for electrical engineering automation approach [J].
Corrêa, JM ;
Farret, FA ;
Canha, LN ;
Simoes, MG .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2004, 51 (05) :1103-1112
[8]   A three-phase line-interactive UPS system implementation with series-parallel active power-line conditioning capabilities [J].
da Silva, SAO ;
Donoso-Garcia, PF ;
Cortizo, PC ;
Seixas, PF .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2002, 38 (06) :1581-1590
[9]   Three-port bidirectional converter for hybrid fuel cell systems [J].
Duarte, Jorge L. ;
Hendrix, Marcel ;
Simoes, Marcelo Godoy .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2007, 22 (02) :480-487
[10]   Repetitive. based controller for a UPS inverter to compensate unbalance and harmonic distortion [J].
Escobar, G. ;
Valdez, A. A. ;
Leyva-Ramos, J. ;
Mattavelli, P. .