Time-domain distance protection for a wind power system considering parameters of the remote end system and influence of outgoing line distribution parameters

被引:0
作者
Hou J. [1 ]
Song G. [1 ]
Chang P. [1 ]
Chang N. [1 ]
Li X. [2 ]
Wu D. [2 ]
机构
[1] School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
[2] NARI Group Corporation, State Grid Electric Power Research Institute Co., Ltd., Nanjing
来源
Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control | 2022年 / 50卷 / 05期
关键词
Distance protection; Distributed parameter model; System from remote end; Time-domain; Wind power system;
D O I
10.19783/j.cnki.pspc.210701
中图分类号
学科分类号
摘要
There is a problem of the limits of existing time-domain distance protection when it comes to a grounding fault with high fault resistance occurring at the end of distance section I in a wind power system long transmission line. This paper presents a time-domain distance protection algorithm for a wind power system long line based on the distributed parameter model and the remote end system parameters. The performance of existing time-domain distance protection under the influences of a long line and remote-end system are discussed. Taking into account the distributed parameter effect of the long line, the near-end electrical quantity is calculated to the compensation point at the end of section I on the long line. The time-domain fault loop equation considering the parameters of the remote end system is constructed between the compensation point and the fault branch, and the fault location is obtained by calculating equations. Combined with the protection setting value, the distance protection criterion is realized. Simulation results show that the proposed protection principle considers the influence of a long line distribution parameters and is suitable for long transmission lines. In addition, when a grounding fault with 300 Ω fault impedance occurs at the end of section I for a long line, the protection can still operate correctly by considering the impact on the end system and is less affected by interference factors such as sampling rate. © 2022 Power System Protection and Control Press.
引用
收藏
页码:106 / 116
页数:10
相关论文
共 25 条
  • [11] LUO Rui, FAN Yanfang, LIU Qunjie, Research on anti-transition resistance single-phase ground distance protection of AC-DC hybrid power system based on time-domain, Proceedings of the CSU-EPSA, 31, 12, pp. 123-129, (2019)
  • [12] YANG Zengli, KONG Xiangping, WANG Lijun, Et al., Distance protection scheme for interconnection line of doubly-fed induction generator based wind farm, Transactions of China Electrotechnical Society, 31, 24, pp. 252-260, (2016)
  • [13] WANG Chunyou, SHU Hongchun, SUN Shiyun, Et al., Time domain distance protection of the collector line of the double-fed wind power farm based on measured data, Power System and Clean Energy, 36, 9, pp. 113-121, (2020)
  • [14] FAN Xiaohong, SUN Shiyun, WANG Chunyou, Et al., Time domain distance protection for asymmetric faults of an outgoing line in doubly-fed wind farms, Power System Protection and Control, 48, 23, pp. 82-91, (2020)
  • [15] HOU Junjie, FAN Yanfang, WANG Yibo, Research on time doman distance protection of parameter identification for cluster wind power transmission line, Power System Protection and Control, 46, 5, pp. 46-53, (2018)
  • [16] JIA Ke, YANG Zhe, ZHAO Qijuan, Et al., High-frequency fault component based distance protection for transmission lines connected to renewable energy power plants, Power System Technology, 43, 9, pp. 3271-3280, (2019)
  • [17] HOU Junjie, FAN Yanfang, Time domain distance protection for long distance outgoing line of wind power system based on distributed parameter model, Power System Protection and Control, 46, 19, pp. 26-33, (2018)
  • [18] SONG G, CHU X, GAO S, Et al., Novel distance protection based on distributed parameter model for long-distance transmission lines, IEEE Transactions on Power Delivery, 28, 4, pp. 2126-2123, (2013)
  • [19] SUONAN J, ZHANG J, JIAO Z, Et al., Distance protection for HVDC transmission lines considering frequency-dependent parameters, IEEE Transactions on Power Delivery, 28, 2, pp. 723-732, (2013)
  • [20] WEN Minghao, WANG Yuxi, CHEN Yu, Et al., Protection of high voltage AC transmission lines based on equal transfer process, Smart Power, 47, 12, pp. 22-29, (2019)