Thermal environmental interference with airborne bacteria and fungi levels in air-conditioned offices

被引:20
作者
Wong, L. T. [1 ]
Mui, K. W. [1 ]
Hui, P. S. [1 ]
Chan, W. Y. [1 ]
Law, A. K. Y. [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Hong Kong, Hong Kong, Peoples R China
关键词
offices; air temperature; bacteria; humidity; microbes;
D O I
10.1177/1420326X08089260
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Indoor airborne bacteria and fungi levels can be selected as indicators of a healthy indoor environment. This study investigated the relationships between the airborne bacteria levels, fungi levels, and thermal environmental parameters, i.e., air temperature and relative humidity, in some offices with a Mechanical Ventilation and Air-Conditioning (MVAC) system operating. A total of 101 samples were collected from two typical Hong Kong air-conditioned office premises. There was evidence that the operation of the MVAC system would have significant influence on both of the indoor airborne bacteria and fungi levels. The results showed that no significant difference in airborne bacteria and fungi levels was observed between offices having similar thermal environments (p > 0.05). However, significantly higher airborne bacteria and fungi levels were found in the same office during non-office hours when the air-conditioning system was shut down (p < 0.03). It was also reported that the airborne bacteria and fungi levels would be correlated with the thermal environmental parameters in some offices (p < 0.0001).
引用
收藏
页码:122 / 127
页数:6
相关论文
共 24 条
[1]  
ACGIH, 1989, AM C GOV IND HYG CIN
[2]  
[Anonymous], 2003, J OCCUP ENVIRON MED, V45, P470
[3]   Why, when and how do HVAC-systems pollute the indoor environment and what to do about it?: the European AIRLESS project [J].
Bluyssen, PM ;
Cox, C ;
Seppänen, O ;
Fernandes, ED ;
Clausen, G ;
Müller, B ;
Roulet, CA .
BUILDING AND ENVIRONMENT, 2003, 38 (02) :209-225
[4]  
Cox C. S., 1995, P11
[5]   AN INVESTIGATION OF THE RELATIONSHIP BETWEEN MICROBIAL AND PARTICULATE INDOOR AIR-POLLUTION AND THE SICK BUILDING SYNDROME [J].
HARRISON, J ;
PICKERING, CAC ;
FARAGHER, EB ;
AUSTWICK, PKC ;
LITTLE, SA ;
LAWTON, L .
RESPIRATORY MEDICINE, 1992, 86 (03) :225-235
[6]   Survey of unsatisfactory levels of airborne bacteria in air-conditioned offices [J].
Hui, P. S. ;
Wong, L. T. ;
Mui, K. W. ;
Law, K. Y. .
INDOOR AND BUILT ENVIRONMENT, 2007, 16 (02) :130-138
[7]   An epistemic indoor air quality assessment protocol for air-conditioned offices [J].
Hui, P. S. ;
Wong, L. T. ;
Mui, K. W. .
INDOOR AND BUILT ENVIRONMENT, 2007, 16 (02) :139-147
[8]   Characteristics of bioaerosol profile in office buildings in Hong Kong [J].
Law, AKY ;
Chau, CK ;
Chan, GYS .
BUILDING AND ENVIRONMENT, 2001, 36 (04) :527-541
[9]   Investigation of indoor air quality at residential homes in Hong Kong - case study [J].
Lee, SC ;
Li, WM ;
Ao, CH .
ATMOSPHERIC ENVIRONMENT, 2002, 36 (02) :225-237
[10]  
Levetin E., 1995, BIOAEROSOLS, P87