Numerical assessment on the thermal imbalance of multiple ground heat exchangers connected in parallel

被引:13
作者
Chen, Fei [1 ]
Mao, Jinfeng [2 ]
Zhu, Guodong [1 ]
Zhang, Bing [1 ]
Tian, Yongjie [1 ]
Liao, Dan [1 ]
Liu, Ying [1 ]
机构
[1] Beijing Special Engn Design & Res Inst, Beijing 100028, Peoples R China
[2] Arrny Engn Univ PLA, Coll Def Engn, Nanjing 210007, Peoples R China
关键词
Multiple ground heat exchangers; Boundary conditions; Thermal imbalance; Load ratios; Borehole field layouts and scales; FINITE-ELEMENT FORMULATION; OPERATION; PERFORMANCE; SIMULATION; EFFICIENCY; BOREHOLES; SYSTEMS; STORAGE; MODEL;
D O I
10.1016/j.geothermics.2021.102191
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Thermal imbalance is a common problem in ground source heat pump (GSHP) systems, especially those with large scale multiple ground heat exchangers (GHEs). It usually happens due to the imbalance between the accumulated heat extracted from and injected into the soil and can lead to heat or cold accumulation, cooling or heating performance deterioration and even system failure. In most projects, the GHEs are not independent of each other, but are connected in parallel as an entirety. Therefore, the interconnections among each GHE within the borehole field should be considered. In this study, a numerical approach considering models of the heat pump and the water separator/collector was established for the thermal imbalance evaluation of multiple GHEs connected in parallel, and it was validated by an in-situ test of a single GHE. The necessity of introducing such models was discussed, and the effects of load ratios, borehole layouts, and scales were also investigated. Results show that when both the heat pump and the water separator/collector were considered, the temperature distribution of the borehole field was always uniform during the five-year operation with the highest temperature unevenness value of 0.37 degrees C, proving that the self-adjusting mechanism of the GHE load (i.e., the GHE load distribution of the borehole field is able to be optimized automatically according to the heat transfer condition of each GHE) is beneficial to maintaining the thermal balance of the borehole field. However, when the interconnections among the GHEs are ignored, the thermal imbalance of the borehole field is overestimated, in particular, under conditions with large load ratios. With the increase in the field scale, the temperature unevenness value of the borehole field first increases and then decreases whether in square or regular hexagon layouts. The numerical approach in this study is helpful to correctly evaluate the thermal imbalance of the borehole field.
引用
收藏
页数:13
相关论文
共 50 条
  • [21] A novel ground thermal recovery system for horizontal ground heat exchangers in a hot climate
    Sedaghat, Ali
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    ENERGY CONVERSION AND MANAGEMENT, 2020, 224 (224)
  • [22] Numerical Investigation on Auxiliary Heat Sources for Horizontal Ground Heat Exchangers
    Bulmez, Alexandru-Mihai
    Ciofoaia, Vasile
    Nastase, Gabriel
    Dragomir, George
    Brezeanu, Alin-Ionut
    Iordan, Nicolae-Fani
    Bolocan, Sorin-Ionut
    Fratu, Mariana
    Plescan, Costel
    Cazacu, Christiana Emilia
    Deaconu, Ovidiu
    BUILDINGS, 2022, 12 (08)
  • [23] Study of Ground Heat Exchangers in the Form of Parallel Horizontal Pipes Embedded in the Ground
    Neupauer, Krzysztof
    Pater, Sebastian
    Kupiec, Krzysztof
    ENERGIES, 2018, 11 (03):
  • [24] The influence of ground heat exchangers operation modes on the ground thermal accumulation
    Zhao, Tiantian
    Yu, Mingzhi
    Rang, Hongmei
    Zhang, Kai
    Fang, Zhaohong
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3909 - 3915
  • [25] Experimental and numerical investigation of heat transfer performance and sustainability of deep borehole heat exchangers coupled with ground source heat pump systems
    Cai, Wanlong
    Wang, Fenghao
    Liu, Jun
    Wang, Zhihua
    Ma, Zhenjun
    APPLIED THERMAL ENGINEERING, 2019, 149 : 975 - 986
  • [26] Numerical investigation on thermal performance of ground heat exchangers using phase change materials as grout for ground source heat pump system
    Qi, Di
    Pu, Liang
    Sun, Futao
    Li, Yanzhong
    APPLIED THERMAL ENGINEERING, 2016, 106 : 1023 - 1032
  • [27] Improved method and case study of thermal response test for borehole heat exchangers of ground source heat pump system
    Wang, Huajun
    Qi, Chengying
    Du, Hongpu
    Gu, Jihao
    RENEWABLE ENERGY, 2010, 35 (03) : 727 - 733
  • [28] Numerical evaluation on the effects of soil freezing on underground temperature variations of soil around ground heat exchangers
    Yang, Weibo
    Kong, Lei
    Chen, Yongping
    APPLIED THERMAL ENGINEERING, 2015, 75 : 259 - 269
  • [29] Thermal investigation of in-series vertical ground heat exchangers for industrial waste heat storage
    Cui, Ping
    Diao, Nairen
    Gao, Chengmiao
    Fang, Zhaohong
    GEOTHERMICS, 2015, 57 : 205 - 212
  • [30] Numerical investigation on the underground thermal imbalance of ground-coupled heat pump operated in cooling-dominated district
    Yang, Weibo
    Chen, Yongping
    Shi, Mingheng
    Spitler, Jeffrey D.
    APPLIED THERMAL ENGINEERING, 2013, 58 (1-2) : 626 - 637