Feature Extraction and Comprehension of Partial Discharge Characteristics in Transformer Oil from Rated AC Frequency to Very Low Frequency

被引:2
作者
Zhou, Zhongliu [1 ]
Zhou, Yuanxiang [1 ,2 ]
Huang, Xin [1 ]
Zhang, Yunxiao [1 ]
Wang, Mingyuan [3 ]
Guo, Shaowei [4 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Elect Power Syst, Beijing 100084, Peoples R China
[2] Xinjiang Univ, Sch Elect Engn, Urumqi 830047, Peoples R China
[3] State Grid Jibei Elect Econ Res Inst, Beijing 100045, Peoples R China
[4] North China Elect Power Res Inst Co Ltd, Beijing 100045, Peoples R China
关键词
partial discharge; low frequency voltage; PRPD; characteristic parameter; insulation defect diagnosis; 0.1; HZ; RECOGNITION; BEHAVIOR; CAVITY; INSULATION; LIQUIDS;
D O I
10.3390/en11071702
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The reactive current can be reduced effectively by decreasing the frequency of the voltage in partial discharge (PD) test, especially for equipment with large capacitance. Thus, the cost and volume of the test power supply can be economized. To figure out the difference of PD characteristics in transformer oil between rated alternating-current (AC) frequency (50 Hz) and low frequency, tests are conducted from rated AC frequency to very low frequency (0.1 Hz) based on impulse current method. The results show that with the decrease of frequency, the inception voltage increases. The maximum and mean magnitude of discharge and pulse repetition rate first increase slightly, then decrease obviously. The main features of the variation of phase resolved PD (PRPD) patterns, discharge statistical patterns (phase distribution of maximum and mean discharge magnitude, pulse repetition rate q(max)-phi, q(mean)-phi, n-phi; and number distribution of discharge magnitude n-q), and their characteristic parameters (skewness S-k(+), S-k(-); kurtosis K-u(+), K-u(-); asymmetry A(sy); and correlation coefficient C-c) are depicted in detail, which should be paid attention to when using low frequency voltage. The inner mechanism for these variations is discussed from the aspects of the influence on electric field distribution and discharge process of frequency. Additionally, the variation trend of PD characteristics with the decrease of frequency can provide more information about insulation defect, which can be the supplement for discharge mode recognition.
引用
收藏
页数:17
相关论文
共 30 条
  • [21] Preliminary Exploration of Oil-immersed Inverted Current Transformer Partial Discharge Identification by Wide Frequency Device
    Qian, Dun
    Yang, Zhi
    Feng, Yuzhe
    2024 IEEE 2ND INTERNATIONAL CONFERENCE ON POWER SCIENCE AND TECHNOLOGY, ICPST 2024, 2024, : 431 - 436
  • [22] Feature Extraction Method for Partial Discharge Pattern in GIS Based on Time-frequency Analysis and Fractal Theory
    Chen J.
    Xu C.
    Li P.
    Shao X.
    Li C.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (01): : 287 - 295
  • [23] Time-frequency Analysis Method for HF Partial Discharge Signal From Power Transformer Bushing Tap With Signal Propagation Characteristics
    Liu Y.
    Xie X.
    Luo X.
    Zhang L.
    Du Z.
    Liu, Yi (liuyi@sgepri.sgcc.com.cn), 1600, Science Press (46): : 594 - 602
  • [24] Partial Discharge Characterization of Cross-Linked Polyethylene Medium Voltage Power Cable Termination Defects at Very Low Frequency (0.1 Hz) and Power Frequency Test Voltages
    Fynes-Clinton, Daniel
    Nyamupangedengu, Cuthbert
    IEEE ELECTRICAL INSULATION MAGAZINE, 2016, 32 (04) : 15 - 23
  • [25] Feature Extraction Method Based on Pulse-Coupled Neural Networks for Ultra High Frequency Partial Discharge in Transformers
    Tang, Ju
    Zhou, Jiabin
    Zhang, Xiaoxing
    Tao, Jiagui
    INTERNATIONAL REVIEW OF ELECTRICAL ENGINEERING-IREE, 2012, 7 (01): : 3270 - 3279
  • [26] A Partial Discharge Signal Separation Method Applicable for Various Sensors Based on Time-Frequency Feature Extraction of t-SNE
    Fu, Yao
    Zhou, Kai
    Zhu, Guangya
    Li, Zerui
    Li, Yuan
    Meng, Pengfei
    Xu, Yefei
    Lu, Lu
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2024, 73 : 1 - 9
  • [27] High-Frequency Partial Discharge Characteristics of Solid-State Transformer Interturn Multilayer Insulation Under Repetitive Electrical Stress
    Li, Zhihui
    Han, Yaoxuan
    Xie, Zengqi
    Ren, Hanwen
    Li, Qingmin
    Wang, Zhongdong
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2024, 71 (10) : 13331 - 13340
  • [28] Comparison of the Characteristics of Corona Discharge in the Oil under Low and Power Frequency Voltage by Impulse-Current Method
    Zhou Y.
    Zhou Z.
    Guo S.
    Niu Z.
    Zhang L.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (01): : 160 - 169
  • [29] Modelling of supply voltage frequency effect on partial discharge repetition rate and charge amplitude from AC to DC at room temperature
    Seri, P.
    Naderiallaf, H.
    Montanari, G. C.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (03) : 764 - 772
  • [30] Difference Analysis of High-voltage Frequency Domain Dielectric and Partial Discharge Characteristics of Oil-paper Insulation Bushings with Typical Defections
    Jian Z.
    Hao J.
    Liu Q.
    Liao R.
    Shang Y.
    Liu Q.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (10): : 4113 - 4123