Retrofitting of an air-cooled data center for energy efficiency

被引:30
作者
Kuzay, Mustafa [1 ,4 ]
Dogan, Aras [1 ,4 ]
Yilmaz, Sibel [1 ]
Herkiloglu, Oguzhan [2 ]
Atalay, Ali Serdar [2 ]
Cemberci, Atilla [2 ]
Yilmaz, Cagatay [3 ]
Demirel, Ender [1 ,4 ]
机构
[1] Design & Simulat Tech Inc, TR-26480 Eskisehir, Turkey
[2] Radius Solut Ctr, Bahar Arkasi St 11, TR-34692 Istanbul, Turkey
[3] Lande Ind Met Prod Inc Co, Organized Ind Zone, 20th St 14, Eskisehir, Turkey
[4] Eskisehir Osmangazi Univ, TR-26480 Eskisehir, Turkey
关键词
Data center; Thermal efficiency; Cooling efficiency; CFD modeling; Open-source; MANAGEMENT;
D O I
10.1016/j.csite.2022.102228
中图分类号
O414.1 [热力学];
学科分类号
摘要
Small-scale data centers suffering from low cooling efficiency consume an intense power for reliable operation of IT equipment. In this study, thermal distribution in an air-cooled data center is simulated using an open source Computational Fluid Dynamics (CFD) model to examine the underlying mechanism that reduces thermal and cooling efficiencies. The numerical model is validated with the temperature measurements conducted in the data center. Numerical simulations have revealed that recirculating hot flows observed at the top of the racks increased the air temperature beyond the allowable maximum temperature. To this end, the data center has been retrofitted by creating a hot aisle with the implementation of a moving baffle at the rear of the rack. Numerical simulations conducted for two working scenarios have demonstrated that such a minor modification could result in remarkable enhancement in the cooling efficiency. Efficiency of the data center has improved by 47.2% and 22.7% with respect to the RCI (Rack Cooling Index) and RHI (Return Heat Index), respectively. The present numerical model can capture distributions of the efficiency metrics over the racks. Present methodology can be used to reduce power consumption by the cooling and ventilation systems in existing data centers.
引用
收藏
页数:14
相关论文
共 31 条
[31]   Retrofit of Air-Conditioning System in Data Center Using Separate Heat Pipe System [J].
Zheng, Yuwei ;
Li, Zhen ;
Liu, Xiaohua ;
Tong, Zhen ;
Tu, Rang .
PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 2: HVAC&R COMPONENT AND ENERGY SYSTEM, 2014, 262 :685-694