Open-Circuit Fault Diagnosis and Fault-Tolerant Control for a Grid-Connected NPC Inverter

被引:201
作者
Choi, Ui-Min [1 ]
Lee, June-Seok [2 ]
Blaabjerg, Frede [1 ]
Lee, Kyo-Beum [2 ]
机构
[1] Aalborg Univ, Dept Energy Technol, Ctr Reliable Power Elect, DK-9220 Aalborg, Denmark
[2] Ajou Univ, Dept Elect & Comp Engn, Suwon 443749, South Korea
关键词
Fault detection; fault-tolerant control; grid-connected inverter; neutral-point clamped (NPC) inverter; open-circuit fault; reliability; MOTOR-DRIVES; RELIABILITY; VOLTAGE; CONVERTERS; ALGORITHM; FAILURE;
D O I
10.1109/TPEL.2015.2510224
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an open-circuit fault detection method for a grid-connected neutral-point clamped (NPC) inverter system. Further, a fault-tolerant control method under an open-circuit fault in clamping diodes is proposed. Under the grid-connected condition, it is impossible to identify the location of a faulty switch by the conventional methods which usually use the distortion of outputs because the distortion of the outputs is the same in some fault cases. The proposed fault detection method identifies the location of the faulty switch and the faulty clamping diode of the NPC inverter without any additional hardware or complex calculations. In the case of the clamping diode faults, the NPC inverter can transfer full rated power with sinusoidal currents by the proposed fault-tolerant control. The feasibility of the proposed fault detection and the fault-tolerant control methods for the grid-connected NPC inverter are verified by simulation and experimental results.
引用
收藏
页码:7234 / 7247
页数:14
相关论文
共 28 条
[1]  
Abadi MB, 2012, 2012 XXTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), P1893, DOI 10.1109/ICElMach.2012.6350140
[2]  
ABB, 2015, DAT STRING INV PVI 1
[3]  
[Anonymous], 2008, HDB ROB VAL AUT EL E
[4]  
[Anonymous], 2011, 14 EUROPEAN C POWER
[5]  
[Anonymous], POW MOD REL
[6]   Real-Time IGBT Open-Circuit Fault Diagnosis in Three-Level Neutral-Point-Clamped Voltage-Source Rectifiers Based on Instant Voltage Error [J].
Caseiro, Luis M. A. ;
Mendes, Andre M. S. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (03) :1669-1678
[7]   Study and Handling Methods of Power IGBT Module Failures in Power Electronic Converter Systems [J].
Choi, Ui-Min ;
Blaabjerg, Frede ;
Lee, Kyo-Beum .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (05) :2517-2533
[8]   New Modulation Strategy to Balance the Neutral-Point Voltage for Three-Level Neutral-Clamped Inverter Systems [J].
Choi, Ui-Min ;
Lee, June-Seok ;
Lee, Kyo-Beum .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2014, 29 (01) :91-100
[9]   Diagnosis and Tolerant Strategy of an Open-Switch Fault for T-Type Three-Level Inverter Systems [J].
Choi, Ui-Min ;
Lee, Kyo-Beum ;
Blaabjerg, Frede .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2014, 50 (01) :495-508
[10]   Selected failure mechanisms of modern power modules [J].
Ciappa, M .