Sizing of a Photovoltaic-Wind-Oil Shale Hybrid System: Case Analysis in Jordan

被引:24
作者
AL-Ghussain, Loiy [1 ]
Taylan, Onur [2 ]
Fahrioglu, Murat [3 ]
机构
[1] Middle East Tech Univ, Sustainable Environm & Energy Syst, Northern Cyprus Campus,Guzelyurt Via Mersin 10, TR-99738 Kalkanli, Turkey
[2] Middle East Tech Univ, Mech Engn Program, Northern Cyprus Campus,Guzelyurt Via Mersin 10, TR-99738 Kalkanli, Turkey
[3] Middle East Tech Univ, Elect & Elect Engn Program, Northern Cyprus Campus,Guzelyurt Via Mersin 10, TR-99738 Kalkanli, Turkey
来源
JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME | 2018年 / 140卷 / 01期
关键词
hybrid systems; oil shale; solar; wind; energy economics; energy security; PERFORMANCE;
D O I
10.1115/1.4038048
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The integration between renewable energy systems (RESs) and oil shale system ensures reliable power generation source with a competitive energy generation cost when compared to costs of conventional systems. In addition, this integration will prevent considerable amount of CO2 emissions. This study aims to determine the size of a grid-tied hybrid system in Al-Tafilah, Jordan that maximizes the yearly overall fraction of demand met with levelized cost of electricity (LCOE) equal to or lower than the local cost of electricity generation. In addition, the effect of the integration of lithium-ion batteries as shortterm energy storage systems (ESSs) will be investigated in addition to the effect of carbon social cost on the economics of the system. The maximum FH by the hybrid system in Al-Tafilah is 97.2% with ESS and 96.9% without ESS where 70.4% of the demand is met by the 12MW oil shale system; however, to achieve these fractions, enormous installed capacity of photovoltaic (PV) and wind is required where 99% of the energy production is excess and LCOE is larger than COEcon. The maximum FH with LCOE equals to COEcon can be achieved by 12 MW oil shale, 3.5 MW PV, and 6 MW wind turbines without ESS. Such size will have FH of 87.23%, capacity factor of 46.1%, RES fraction of 16.9%, net present value (NPV) of 34.8 million USD, and a payback period of 4.8 years.
引用
收藏
页数:12
相关论文
共 49 条
  • [21] Development of intelligent MPPT (maximum power point tracking) control for a grid-connected hybrid power generation system
    Hong, Chih-Ming
    Ou, Ting-Chia
    Lu, Kai-Hung
    [J]. ENERGY, 2013, 50 : 270 - 279
  • [22] Analysis of renewable energy situation in Jordan
    Hrayshat, Eyad S.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2007, 11 (08) : 1873 - 1887
  • [23] Viability of solar photovoltaics as an electricity generation source for Jordan
    Hrayshat, Eyad S.
    [J]. RENEWABLE ENERGY, 2009, 34 (10) : 2133 - 2140
  • [24] Jaber J. O., 2004, Clean Technologies and Environmental Policy, V6, P174, DOI 10.1007/S10098-003-0232-9
  • [25] Modelling oil-shale integrated tri-generator behaviour: Predicted performance and financial assessment
    Jaber, JO
    Probert, SD
    Williams, PT
    [J]. APPLIED ENERGY, 1998, 59 (2-3) : 73 - 95
  • [26] Medium-range planning economics of future electrical-power generation options
    Jaber, JO
    Al-Sarkhi, A
    Akash, BA
    Mohsen, MS
    [J]. ENERGY POLICY, 2004, 32 (03) : 357 - 366
  • [27] Kaplan S.M., 2008, Power Plants: Characteristics and Costs
  • [28] Unbalanced distribution network fault analysis with hybrid compensation
    Lin, W. -M.
    Ou, T. -C.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (01) : 92 - 100
  • [29] Empirical validation of models to compute solar irradiance on inclined surfaces for building energy simulation
    Loutzenhiser, P. G.
    Manz, H.
    Felsmann, C.
    Strachan, P. A.
    Frank, T.
    Maxwell, G. M.
    [J]. SOLAR ENERGY, 2007, 81 (02) : 254 - 267
  • [30] Manwell J.F., 2009, WIND