Thermal comfort of people in a super high-rise building with central air-conditioning system in the hot-humid area of China

被引:27
作者
Zhang, Zhongjun [1 ,2 ]
Zhang, Yufeng [2 ]
Khan, Adnan [2 ]
机构
[1] Anyang Inst Technol, Sch Civil & Architectural Engn, Anyang 455000, Peoples R China
[2] South China Univ Technol, Dept Architecture, State Key Lab Subtrop Bldg Sci, Guangzhou 510640, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
Central air-conditioning system; Thermal comfort; Hot-humid areas; Super high-rise building; PMV; FIELD EXPERIMENTS; OFFICE BUILDINGS; PMV MODEL; TEMPERATURE; ENVIRONMENT; CLASSROOMS; CLIMATES; ENERGY;
D O I
10.1016/j.enbuild.2019.109727
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Built areas with centralized air conditioning systems have increased intensively in recent years in the hot-humid area of China's mainland. A longitudinal field survey was conducted in a super high-rise building with central air-conditioning system in Guangzhou for a whole year. Forty-four respondents participated in the survey: they were visited three times a week, and thermal comfort data on a large scale with sample size of 3,345 were obtained, containing indoor environmental parameters, personal factors, and subjective responses. The data analysis showed that the indoor environments varied in small operative temperature ranges of 22 degrees C-27 degrees C in summer and 19 degrees C-25 degrees C in non-summer months, with moderate relative humidity and an air speed of 0.1 m/s. The respondents' clothing insulation changed in a narrow range of 0.55 clo to 0.60 clo in summer and in a wide range of 0.80 clo to 0.90 clo in non-summer months. The thermal neutral and acceptable operative temperatures were 27.9 degrees C and 22.0 degrees C-29.5 degrees C in summer, and the thermal neutral temperature was 24.5 degrees C in non-summer months. A strong preference for a cooler environment was identified in summer. The PMV (Predicted Mean Vote) model was confirmed to be not applicable in, the adaptive thermal comfort theory is also applicable to people in centrally air-conditioned buildings. This study provides a better understanding of thermal comfort in centrally air-conditioned indoor environment, and it is beneficial to practices regarding the evaluation, design, and control of indoor environments for centrally air-conditioned buildings in the hot-humid area of China's mainland. (C) 2019 Elsevier B.V. All rights reserved.
引用
收藏
页数:11
相关论文
共 44 条
  • [11] Field study on adaptive thermal comfort in office buildings in Malaysia, Indonesia, Singapore, and Japan during hot and humid season
    Damiati, Siti Aisyah
    Zaki, Sheikh Ahmad
    Rijal, Hom Bahadur
    Wonorahardjo, Surjamanto
    [J]. BUILDING AND ENVIRONMENT, 2016, 109 : 208 - 223
  • [12] de Dear R., 1997, Final Report on RP-884
  • [13] de Dear R.J., 1994, ASHRAE T, V100, P457
  • [14] THERMAL COMFORT IN THE HUMID TROPICS - FIELD EXPERIMENTS IN AIR-CONDITIONED AND NATURALLY VENTILATED BUILDINGS IN SINGAPORE
    DEDEAR, RJ
    LEOW, KG
    FOO, SC
    [J]. INTERNATIONAL JOURNAL OF BIOMETEOROLOGY, 1991, 34 (04) : 259 - 265
  • [15] Thermal comfort: A review paper
    Djongyang, Noel
    Tchinda, Rene
    Njomo, Donatien
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2010, 14 (09) : 2626 - 2640
  • [16] Field study on adaptive thermal comfort in typical air conditioned classrooms
    Fang, Zhaosong
    Zhang, Sheng
    Cheng, Yong
    Fong, Alan M. L.
    Oladokun, Majeed Olaide
    Lin, Zhang
    Wu, Huijun
    [J]. BUILDING AND ENVIRONMENT, 2018, 133 : 73 - 82
  • [17] Fanger PO, 2002, ENERG BUILDINGS, V34, P533
  • [18] Thermal comfort analysis of PMV model Prediction in Air conditioned and Naturally Ventilated Buildings
    Gilani, Syed Ihtsham ul Haq
    Khan, Muhammad Hammad
    Pao, William
    [J]. CLEAN, EFFICIENT AND AFFORDABLE ENERGY FOR A SUSTAINABLE FUTURE, 2015, 75 : 1373 - 1379
  • [19] Hussein I., 2010, INT C EN ENV IEEE MA, P360
  • [20] Hwang R.L., 2007, Open Constr. Build. Technol. J, V1, P8, DOI [10.2174/1874836800701010008, DOI 10.2174/1874836800701010008]