Assessment of moisture contents in paper-oil insulation with advanced ageing processes

被引:0
|
作者
Szrot, Marek [1 ]
Subocz, Jan [1 ]
机构
[1] ZUT, Katedra Elektrotechnol & Diagnostyki, PL-70313 Szczecin, Poland
来源
PRZEGLAD ELEKTROTECHNICZNY | 2010年 / 86卷 / 11B期
关键词
water content; aged paper-oil insulation; FDS; RVM; PDC; sludges;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Experiences in moisture contents assessment in paper-oil insulation of transformers with advanced ageing processes have been presented. It was found that joint measurement RVM+PDC increases quality of assessment, especially for transformers with non-homogenous morphology of insulation. For water contents in cellulose higher that 3% it is necessary to take into consideration for analysis results of oil tests. The measurement RVM+PDC after considering oil tests allows to identify deposits on the active part of transformers. (Assessment of moisture contents in paper-oil insulation with advanced ageing processes)
引用
收藏
页码:170 / 173
页数:4
相关论文
共 50 条
  • [31] Application of Aging Studies to the Evaluation of Paper-Oil Insulation of Power Capacitors.
    Buck, Jozef
    Przeglad Elektrotechniczny, 1972, 48 (10): : 452 - 455
  • [32] Model building for current transformer paper-oil insulation state diagnostics
    Skrupskaya, L. S.
    Oliinyk, A. O.
    Sakhno, A. A.
    ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2014, (02) : 48 - 51
  • [33] Structure of Paper-Oil Insulation for Mass-Impregnated HVDC Cables
    Hakonseth, G.
    Furuheim, K. M.
    Ildstad, E.
    2019 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2019, : 524 - 527
  • [34] Diagnostics of the paper-oil insulation condition using selected parameters of recovery voltage
    Wolny, Stefan
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 214 - 217
  • [35] Modeling of Early Stage Partial Discharge and Overheating Degradation of Paper-oil Insulation
    Tsuchie, Motoo
    Kozako, Masahiro
    Hikita, Masayuki
    Sasaki, Ei
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) : 1342 - 1349
  • [36] Application of multifactorial variance analysis for assessment of temperature influence on selected parameters of recovery voltage of paper-oil insulation
    Wolny, Stefan
    Kedzua, Jozef
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 218 - 221
  • [37] Evaluation via PEA measurements of paper-oil insulation submitted to gamma radiation
    Ciobanu, R.
    Schreiner, C.
    Olariu, M.
    PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 1187 - 1190
  • [39] Evaluation of Moisture Content In Paper-Oil of Aged Power Transformer Using RVM
    Dwivedi, C. K.
    Daigavane, M. B.
    2009 SECOND INTERNATIONAL CONFERENCE ON EMERGING TRENDS IN ENGINEERING AND TECHNOLOGY (ICETET 2009), 2009, : 963 - +
  • [40] Measurement of the Dielectric Properties of Paper-Oil Cables and the Cellulose-Oil Insulation System of Power Transformers
    Menzel, Johannes
    Patsch, Rainer
    Kamenka, Dieter
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 1020 - +