Assessment of moisture contents in paper-oil insulation with advanced ageing processes

被引:0
|
作者
Szrot, Marek [1 ]
Subocz, Jan [1 ]
机构
[1] ZUT, Katedra Elektrotechnol & Diagnostyki, PL-70313 Szczecin, Poland
来源
PRZEGLAD ELEKTROTECHNICZNY | 2010年 / 86卷 / 11B期
关键词
water content; aged paper-oil insulation; FDS; RVM; PDC; sludges;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Experiences in moisture contents assessment in paper-oil insulation of transformers with advanced ageing processes have been presented. It was found that joint measurement RVM+PDC increases quality of assessment, especially for transformers with non-homogenous morphology of insulation. For water contents in cellulose higher that 3% it is necessary to take into consideration for analysis results of oil tests. The measurement RVM+PDC after considering oil tests allows to identify deposits on the active part of transformers. (Assessment of moisture contents in paper-oil insulation with advanced ageing processes)
引用
收藏
页码:170 / 173
页数:4
相关论文
共 50 条
  • [1] Influence of sludge on electric processes in paper-oil insulation
    Zenker, Marek
    Mrozik, Andrzej
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (11B): : 334 - 336
  • [2] Study on the Impact of Initial Moisture Contents on Ageing Characteristics of Transformer Oil-paper Insulation
    Xia, Guoqiang
    Wu, Guangning
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [3] Near infrared spectroscopy as diagnostic method of moisture content in paper-oil insulation
    Brodka, Boleslaw
    Moscicka-Grzesiak, Hanna
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 136 - 140
  • [4] Assessment of transformer insulation condition by evaluation of paper-oil system.
    Murthy, TSR
    IEEE 1996 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS I & II, 1996, : 332 - 335
  • [5] Accelerated Ageing Study of Transformer Paper-oil Insulation under Repetitive Transient Conditions
    Devadiga, A. A.
    Jayaram, S. H.
    2022 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP 2022), 2022, : 61 - 64
  • [6] Ageing studies on paper-oil to assess the condition of solid insulation used in Power Transformers
    Thomas, P
    Shukla, AK
    Raghuveer
    ICSD '01: PROCEEDINGS OF THE 2001 IEEE 7TH INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS, 2001, : 69 - 72
  • [7] Investigation of temperature effects on the ageing of paper-oil insulation under repetitive transient voltages
    Arabul, Ahmet Yigit
    Arabul, Fatma Keskin
    Jayaram, Shesha H.
    2023 IEEE ELECTRICAL INSULATION CONFERENCE, EIC, 2023,
  • [8] PAPER-OIL INSULATION - NEW DEFINITION OF DAMAGE
    ASENJO, E
    EIDELSTEIN, G
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1978, 13 (03): : 179 - 183
  • [9] The program for evaluation of moisture content in paper-oil insulation using artificial neural networks
    Bernat, Jakub
    Gielniak, Jaroslaw
    Moranda, Hubert
    PRZEGLAD ELEKTROTECHNICZNY, 2008, 84 (10): : 5 - 7
  • [10] Moisture equilibrium in transformer paper-oil systems
    Du, Y
    Zahn, M
    Lesieutre, BC
    Mamishev, AV
    Lindgren, SR
    IEEE ELECTRICAL INSULATION MAGAZINE, 1999, 15 (01) : 11 - 20