Breakdown voltage of electrode arrangements in vacuum circuit breakers

被引:28
作者
Schümann, U [1 ]
Giere, S [1 ]
Kurrat, M [1 ]
机构
[1] Tech Univ Carolo Wilhelmina Braunschweig, Inst High Voltage & Elect Power Syst, D-38106 Braunschweig, Germany
关键词
area effect; dielectric strength; tube design; surface condition;
D O I
10.1109/TDEI.2003.1219637
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The prediction of HV strength of electrode arrangements in vacuum is complex. A comparison of experimental results from different labs is quite difficult, because they are influenced by a wide range of parameters like electrode material, surface finish, surface area, conditioning state of the surface and the geometry of the electrode arrangement. The aim of this work is to find an empirical relation between the breakdown voltage and different electrodes parameters. Shielding arrangements and main contacts of vacuum tubes are of particular interest. For this purpose, models of contacts and shield electrodes made of stainless steel are stressed with lightning impulse voltage. Several methods of surface finishing are applied to obtain reproducible conditions. The experimental results and deliberations for an empirical approach are presented. In addition the results are related to numerical field calculations.
引用
收藏
页码:557 / 562
页数:6
相关论文
共 6 条
[1]  
[Anonymous], 1996, 4288 ISO
[2]  
KUCHLER A, 1996, HOCHSPANNUNGS TECHNI
[3]  
Latham R., 1995, HIGH VOLTAGE VACUUM
[4]   AREA EFFECT ON ELECTRIC BREAKDOWN OF COPPER AND STAINLESS-STEEL ELECTRODES IN VACUUM [J].
OKAWA, M ;
SHIOIRI, T ;
OKUBO, H ;
YANABU, S .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1988, 23 (01) :77-81
[5]  
SENTKER P, 1998, THESIS TU BRAUNSCHWE
[6]   Vacuum interrupters: The new technology for switching and protecting distribution circuits [J].
Slade, PG .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1997, 33 (06) :1501-1511