Impact of Tie-Line Power on Inter-Area Modes With Increased Penetration of Wind Power

被引:33
作者
Garmroodi, Mehdi [1 ]
Hill, David J. [1 ,2 ]
Verbic, Gregor [1 ]
Ma, Jin
机构
[1] Univ Sydney, Sch Elect & Informat Engn, Sydney, NSW 2000, Australia
[2] Univ Hong Kong, Dept Elect & Elect Engn, Hong Kong, Hong Kong, Peoples R China
关键词
Damping; inertia; small-signal stability; tie-line power; wind turbine generator; GENERATORS;
D O I
10.1109/TPWRS.2015.2477536
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper studies the impact of displacing conventional synchronous generators with wind turbine generators (WTGs) on the damping of inter-area modes. The impact of tie-line power, which can be beneficial or detrimental with increased wind penetration on the damping of the inter-area mode in a two-area test system, is investigated. It is seen that the inter-area modes are more prone to instability when areas with high wind penetrations export power to remote areas. Furthermore, the performance of supplementary controllers in WTGs (i.e., terminal voltage control and inertia emulation) on the inter-area modes are evaluated. The results show that the controllers can mitigate the possible adverse effects of increased penetration of wind power on the inter-area modes. The results of the studies on the two area system are used to guide a study on a 14-generator model of the Australian grid.
引用
收藏
页码:3051 / 3059
页数:9
相关论文
共 21 条
[1]  
[Anonymous], MODELING GE WIND TUR
[2]  
[Anonymous], 2013, Planificacion Central del SING. Informe
[3]   Future on Power Electronics for Wind Turbine Systems [J].
Blaabjerg, Frede ;
Ma, Ke .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2013, 1 (03) :139-152
[4]   Frequency response capability of full converter wind turbine generators in comparison to conventional generation [J].
Conroy, James F. ;
Watson, Rick .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2008, 23 (02) :649-656
[5]   Small Signal Stability Assessment of Power Systems With Increased Penetration of Photovoltaic Generation: A Case Study [J].
Eftekharnejad, Sara ;
Vittal, Vijay ;
Heydt, Gerald Thomas ;
Keel, Brian ;
Loehr, Jeffrey .
IEEE TRANSACTIONS ON SUSTAINABLE ENERGY, 2013, 4 (04) :960-967
[6]   Impact of Increased Penetration of DFIG-Based Wind Turbine Generators on Transient and Small Signal Stability of Power Systems [J].
Gautam, Durga ;
Vittal, Vijay ;
Harbour, Terry .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2009, 24 (03) :1426-1434
[7]  
Gibbard M., 2010, Simplified 14-Generator model of the SE Australian power system (Revision 3)
[8]  
Global Wind Energy Council, GLOB CUM INST CAP 19
[9]   APPLICATION OF PRONY ANALYSIS TO THE DETERMINATION OF MODAL CONTENT AND EQUIVALENT MODELS FOR MEASURED POWER-SYSTEM RESPONSE [J].
HAUER, JF .
IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (03) :1062-1068
[10]  
Kundur P., 1994, Power system stability and control