A New method for the Calculation of Leakage Reactance in Power Transformers

被引:20
作者
Dawood, Kamran [1 ]
Alboyaci, Bora [2 ]
Cinar, Mehmet Aytac [3 ]
Sonmez, Olus [4 ]
机构
[1] Kocaeli Univ, Dept Elect Engn, Fac Engn, Izmit, Turkey
[2] Kocaeli Univ, Dept Elect, Fac Engn, Izmit, Turkey
[3] Kocaeli Univ, Izmit Vocat Sch, Izmit, Turkey
[4] Sonmez Transformer Co, Istasyon Mahallesi 1495-1 Sokak, TR-41410 Gebze, Turkey
关键词
Energy method; Finite element method; Leakage reactance; Transformer;
D O I
10.5370/JEET.2017.12.5.1883
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformers are one of the most precious elements of the electric power system. Stability and reliability of the electric power network mainly depend on the working of the transformer. Leakage reactance of the transformer is one of the important factors and accurate calculation of the leakage reactance is necessary for the transformer designers and electric distributors. Leakage reactance of the transformer depends on the geometry of the transformer. There are many different methods for the calculations of the leakage reactance however mostly are usable when the axial heights of the high voltage and low voltage windings are equal. When the axial heights of high voltage and low voltage windings are asymmetric most of the analytical methods are not reliable. In this study, a new analytical method is introduced for the calculation of the leakage reactance. Fourteen different transformers are investigated in this study and four of them are presented in this paper. The results of the new analytical method are compared with the experimental results. Other analytical and numerical methods are also compared with this new method. Results show that this method is more reliable and accurate as compared to the other analytical methods. The maximum relative error between short-circuit test and proposed method for these fourteen transformers was less than 2.8%.
引用
收藏
页码:1883 / 1890
页数:8
相关论文
共 18 条
[11]  
Rabins L., 1956, Transactions of the American Institute of Electrical Engineers, Part I: Communication and Electronics, V75, P261, DOI DOI 10.1109/TCE.1956.6372526
[12]  
Rao S., 1982, FINITE ELEMENT METHO
[13]   Finite-element calculation of leakage inductances of a saturated salient-pole synchronous machine with damper circuits [J].
Shima, K ;
Ide, K ;
Takahashi, M .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2002, 17 (04) :463-470
[14]   Study on the Transfer Functions for Detecting Windings Displacement of Power Transformers with Impulse Method [J].
Shon, Chae-Hwa ;
Yi, Sang-Hwa ;
Lee, Heun-Jin ;
Kang, Dong-Sik .
JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2012, 7 (06) :876-883
[15]  
Silvester PP., 1990, FINITE ELEMENTS ELEC, V2nd
[16]   ANALYSIS OF 3-D MAGNETIC-FIELDS IN HIGH LEAKAGE REACTANCE TRANSFORMERS [J].
TOMCZUK, B .
IEEE TRANSACTIONS ON MAGNETICS, 1994, 30 (05) :2734-2738
[17]  
Tomczuk Bronislaw, 1992, IEEE T MAGNETIC, V28
[18]   CALCULATIONS OF SELF AND MUTUAL IMPEDANCES BETWEEN SECTIONS OF TRANSFORMER WINDINGS [J].
WILCOX, DJ ;
HURLEY, WG ;
CONLON, M .
IEE PROCEEDINGS-C GENERATION TRANSMISSION AND DISTRIBUTION, 1989, 136 (05) :308-314