Analysis of the Effect of a Saturable-Core HTS Fault Current Limiter on the Circuit Breaker Transient Recovery Voltage

被引:0
作者
Lopez-Roldan, J.
Price, A. C.
De La Rosa, F.
Moriconi, F.
机构
来源
2011 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING | 2011年
关键词
Fault current limiter; HTS FCL; rate of rise of recovery voltage; saturated-core FCL; transient recovery voltage;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper presents the analysis of transient recovery voltage (TRV) under the presence of a saturable-core high temperature superconducting fault current limiter (HTS FCL). Calculations are performed for the case when an equivalent air core reactor that provides comparable fault current limitation as the FCL is inserted in the line. Simulations are performed using different approaches that comprise the direct solution of the related equations solved in a spreadsheet. This is compared with results obtained using EMTP-RV (R) and PSCAD (R) software simulation tools. The obtained results concur to show that the saturable-core HTS FCL has a significantly lower effect on the rate of rise of the circuit breaker TRV as compared with the air core reactor.
引用
收藏
页数:8
相关论文
共 15 条
  • [1] Evaluation of position of a fault current limiter with regard to the circuit breaker
    Alcida, Anthony Frantz
    Saint Paul, Moreau, Jr.
    Calixte, Evenson
    [J]. 2006 38TH ANNUAL NORTH AMERICAN POWER SYMPOSIUM, NAPS-2006 PROCEEDINGS, 2006, : 475 - +
  • [2] [Anonymous], IEEE5191992
  • [3] [Anonymous], 1989, EL6275 EPRI
  • [4] Bellei TA, 2001, 2001 IEEE/PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION, VOLS 1 AND 2, P603, DOI 10.1109/TDC.2001.971302
  • [5] Reduction of rating required for circuit breakers by employing series-connected fault current limiters
    Calixte, E
    Yokomizu, Y
    Shimizu, H
    Matsumura, T
    Fujita, H
    [J]. IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2004, 151 (01) : 36 - 42
  • [6] *CIGRE WORK GROUP, 2008, GUID IMP FAULT CURR
  • [7] Das J.C., 2002, POWER SYSTEM ANAL SH, DOI DOI 10.1201/9780203908952
  • [8] Greenwood A., 1991, ELECT TRANSIENTS POW, V2nd
  • [9] Moriconi, 2010, P 2010 IEEE PES TRAN
  • [10] Moriconi F, 2010, 2010 IEEE PES C P MI