Energetic, exergetic, environmental and economic assessment of a novel control system for indirect heaters in natural gas city gate stations

被引:35
作者
Ebrahimi-Moghadam, Amir [1 ,2 ]
Deymi-Dashtebayaz, Mahdi [3 ]
Jafari, Hosein [3 ]
Niazmand, Amir [1 ]
机构
[1] Shahrood Univ Technol, Fac Mech Engn, Shahrood, Iran
[2] Aalborg Univ, Dept Energy Technol, Esbjerg, Denmark
[3] Hakim Sabzevari Univ, Ctr Computat Energy, Dept Mech Engn, Sabzevar, Iran
关键词
City gate station; Water bath heater; Fuel consumption; Greenhouse gases emission; Techno-economic analysis; CO2 POWER CYCLE; PRESSURE REDUCTION POINTS; WATER PRODUCTION PROCESS; GEOTHERMAL-ENERGY; SOLAR-ENERGY; DRIVEN; HYDROGEN; OPTIMIZATION; GENERATION; FEASIBILITY;
D O I
10.1007/s10973-020-09413-4
中图分类号
O414.1 [热力学];
学科分类号
摘要
The energy consumption and greenhouse gases emissions in natural gas city gate stations are important issues in the natural gas industry. In order to improve efficiency, have a cleaner environment and achieve economic benefits, the present study aims to propose an optimal system for the indirect water bath heaters in natural gas city gate stations. The optimization procedure is carried out by designing a control system to gain an eligible discharge temperature for the heater based on the gas entry conditions to the city gate station. The controller calculates the temperature of hydrate formation in terms of passing gas pressure and gives this information to the torch of the heater for regulating fuel consumption. A comprehensive study is accomplished based on energy, exergy, environment and economic analysis for different pressure reduction stations. The results indicate that employing the proposed system decreases the amount of fuel consumption and greenhouse gases emissions along with increasing system efficiency. Analyzing the results reveals that using the proposed system leads to a maximum of 28.54% relative increment in the heater efficiency compared to the conventional system (at this condition, the heater efficiency of the conventional and proposed system is eta = 36.12% to eta = 46.43%, respectively). Furthermore, with choosing a heater with a capacity of 100,000 SCMH, it is possible to reduce the pollutants emissions and total costs down to 142.6 tons per year and 3,671,000 $ per year, respectively. [GRAPHICS] .
引用
收藏
页码:2573 / 2588
页数:16
相关论文
共 59 条
[1]   Assessment of a CHP system based on economical, fuel consumption and environmental considerations [J].
Abbasi, Mohammad ;
Deymi-Dashtebayaz, Mahdi ;
Farzaneh-Gord, Mahmood ;
Abbasi, Sedigheh .
INTERNATIONAL JOURNAL OF GLOBAL WARMING, 2015, 7 (02) :256-269
[2]  
ABDI MA, 2002, DESIGN OPERATIONS NA
[3]   Exergoeconomic analysis and optimization of a transcritical CO2 power cycle driven by solar energy based on nanofluid with liquefied natural gas as its heat sink [J].
Abdollahpour, Amir ;
Ghasempour, Roghayeh ;
Kasaeian, Alibakhsh ;
Ahmadi, Mohammad H. .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 139 (01) :451-473
[4]   Thermo-economic analysis and multi-objective optimization of a transcritical CO2 power cycle driven by solar energy and LNG cold recovery [J].
Ahmadi, Mohammad H. ;
Mehrpooya, Mehdi ;
Abbasi, Sara ;
Pourfayaz, Fathollah ;
Bruno, Joan Carles .
THERMAL SCIENCE AND ENGINEERING PROGRESS, 2017, 4 :185-196
[5]   Exergoeconomic analysis and multi objective optimization of performance of a Carbon dioxide power cycle driven by geothermal energy with liquefied natural gas as its heat sink [J].
Ahmadi, Mohammad H. ;
Mehrpooya, Mehdi ;
Pourfayaz, Fathollah .
ENERGY CONVERSION AND MANAGEMENT, 2016, 119 :422-434
[6]  
AKHLAGHI K, 2011, INT J CHEM ENV ENG, V2, P267
[7]  
Al-Megren H., 2012, ADV NATURAL GAS TECH
[8]   A new design for natural gas pressure reduction points by employing a turbo expander and a solar heating set [J].
Arabkoohsar, A. ;
Farzaneh-Gord, M. ;
Deymi-Dashtebayaz, M. ;
Machado, L. ;
Koury, R. N. N. .
RENEWABLE ENERGY, 2015, 81 :239-250
[9]   The minimum gas temperature at the inlet of regulators in natural gas pressure reduction stations (CGS) for energy saving in water bath heaters [J].
Ashouri, Esmail ;
Veysi, Farzad ;
Shojaeizadeh, Ehsan ;
Asadi, Maryam .
JOURNAL OF NATURAL GAS SCIENCE AND ENGINEERING, 2014, 21 :230-240
[10]  