Essential system response information for transient-based leak detection methods

被引:47
作者
Duan, Huan-Feng [1 ]
Lee, Pedro J. [2 ]
Ghidaoui, Mohamed S. [1 ]
Tung, Yeou-Koung [1 ]
机构
[1] Hong Kong Univ Sci & Technol, Dept Civil & Environm Engn, Kowloon, Hong Kong, Peoples R China
[2] Univ Canterbury, Dept Civil & Nat Resources Engn, Christchurch 1, New Zealand
关键词
Inverse transient analysis; leak detection; pipe system; system response function; transient damping; transient reflection; PIPELINES;
D O I
10.1080/00221686.2010.507014
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Many transient-based techniques have been developed for leak detection in piping fluid systems, and they are thought to use leak-induced damping and reflection effects to detect and locate the problem. This work investigates the relative importance of the damping and reflective effects from the leak to the leak detection methods with the importance of both effects tested using four representative methods, which vary significantly in their modes of operation and provide the coverage of the major developments in the transient leak detection field. It was found that all transient-based methods are unable to detect and locate the leak in the absence of the leak-reflected signal, whereas the leak is detected and located even in the absence of leak-induced damping. The results indicate that the information previously thought to be contained in the damping of slow transients was found to be low frequency reflections from the leak.
引用
收藏
页码:650 / 657
页数:8
相关论文
共 26 条
[1]   Leak detection in long pipelines using the least squares method [J].
Al-Khomairi, Abdulrahman .
JOURNAL OF HYDRAULIC RESEARCH, 2008, 46 (03) :392-401
[2]   Transient test-based technique for leak detection in outfall pipes [J].
Brunone, B .
JOURNAL OF WATER RESOURCES PLANNING AND MANAGEMENT-ASCE, 1999, 125 (05) :302-306
[3]  
Brunone B., 2001, Journal of Hydraulic Research, V39, P1
[4]  
Chaudhry M., 1987, APPL HYDRAULIC TRANS
[5]   A selective literature review of transient-based leak detection methods [J].
Colombo, Andrew F. ;
Lee, Pedro ;
Karney, Bryan W. .
JOURNAL OF HYDRO-ENVIRONMENT RESEARCH, 2009, 2 (04) :212-227
[6]   Standing wave difference method for leak detection in pipeline systems [J].
Covas, D ;
Ramos, H ;
de Almeida, AB .
JOURNAL OF HYDRAULIC ENGINEERING-ASCE, 2005, 131 (12) :1106-1116
[7]   Pipe system diagnosis and leak detection by unsteady-state tests. 1. Harmonic analysis [J].
Ferrante, M ;
Brunone, B .
ADVANCES IN WATER RESOURCES, 2003, 26 (01) :95-105
[8]   Wavelets for the analysis of transient pressure signals for leak detection [J].
Ferrante, Marco ;
Brunone, Bruno ;
Meniconi, Silvia .
JOURNAL OF HYDRAULIC ENGINEERING, 2007, 133 (11) :1274-1282
[9]   Leak-edge detection [J].
Ferrante, Marco ;
Brunone, Bruno ;
Meniconi, Silvia .
JOURNAL OF HYDRAULIC RESEARCH, 2009, 47 (02) :233-241
[10]  
Ghidaoui M. S., 2005, Applied Mechanics Review, V58, P49, DOI 10.1115/1.1828050