Environmental noise pollution control of substation by passive vibration and acoustic reduction strategies

被引:21
作者
Fan, Xiaopeng [1 ]
Li, Li [1 ]
Zhao, Li [1 ]
He, Hongming [3 ]
Zhang, Dianhai [2 ]
Ren, Ziyan [2 ]
Zhang, Yanli [2 ]
机构
[1] Guangdong Power Grid Ltd Liabil Corp, Electri Power Res Inst, Guangzhou 510082, Peoples R China
[2] Shengyang Univ Technol, Sch Elect Engn, Shenyang 110870, Peoples R China
[3] Guangdong Power Grid Ltd Liabil Corp, Dongguan Power Supply Bur, Dongguan 52300, Peoples R China
关键词
Acoustic insulation; Distribution transformer; Noise reduction and vibration control; Sound absorbing; Vibration isolation; POWER TRANSFORMER; ACTIVE CONTROL;
D O I
10.1016/j.apacoust.2020.107305
中图分类号
O42 [声学];
学科分类号
070206 ; 082403 ;
摘要
Recently, residents in a specific urban area in China has complained against the noise pollution from a particular indoor substation. This paper aims at solving this problem through experimental investigations on the vibration and noise created by distribution transformers in the substation. Firstly, the noise around the distribution transformers, substation, and in the noise-sensitive room were measured. Secondly, through frequency characteristic analysis, the center frequencies at 250 Hz and 500 Hz with maximum values can be obtained and defined as main frequencies in this paper. Once the frequency of the main noises generated by the distribution transformers are identified, the sound absorbing structure, acoustic insulation structure, and vibration isolators were designed and installed. Following the treatment of noise pollution, the transformer and environment noise were reevaluated. The measurement results show that the integrated strategies proposed lead to effectively inhibiting the distribution transformer noise emitted into the surrounding environment. Consequently, the acoustic environment around the indoor substation was drastically improved. For this case study, the residential bedroom located above the substation is considered as a noise-sensitive room. The measurement following the treatment of noise shows that the average equivalent sound pressure level (SPL) in this room was successfully reduced approximately 6 dB at daytime and 10 dB at night, respectively. The corresponding measurement results illustrate that the SPL satisfied the requirement of limits of the ordinance. (C) 2020 Elsevier Ltd. All rights reserved.
引用
收藏
页数:8
相关论文
共 17 条
[1]  
[Anonymous], 2008, GB 12348-2008
[2]  
[Anonymous], 2008, GB 22337-2008
[3]   Noise and vibration of a power transformer under an electrical excitation [J].
Bouayed, K. ;
Mebarek, L. ;
Lanfranchi, V. ;
Chazot, J. -D. ;
Marechal, R. ;
Hamdi, M. -A. .
APPLIED ACOUSTICS, 2017, 128 :64-70
[4]   Investigation of load noise generation of large power transformer by means of coupled 3D FEM analysis [J].
Ertl, Michael ;
Landes, Hermann .
COMPEL-THE INTERNATIONAL JOURNAL FOR COMPUTATION AND MATHEMATICS IN ELECTRICAL AND ELECTRONIC ENGINEERING, 2007, 26 (03) :788-799
[5]   The role of load harmonics in audible noise of electrical transformers [J].
Ertl, Michael ;
Voss, Stephan .
JOURNAL OF SOUND AND VIBRATION, 2014, 333 (08) :2253-2270
[6]   Development of Ultra-Low-Noise Transformer Technology [J].
Girgis, Ramsis S. ;
Bernesjoe, Mats S. ;
Thomas, Scott ;
Anger, Jan ;
Chu, Donald ;
Moore, Harold R. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) :220-226
[7]   Reduction of Vibration and Sound-Level for a Single-Phase Power Transformer With Large Capacity [J].
Hsu, Chang-Hung ;
Lee, Sau-Lie ;
Lin, Chia-Ching ;
Liu, Chien-Sheng ;
Chang, Shu-Ying ;
Hsieh, Min-Fu ;
Huang, Yi-Mei ;
Fu, Chao-Ming .
IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (11)
[8]   Vibration transmission from internal structures to the tank of an oil-filled power transformer [J].
Jin, Ming ;
Pan, Jie .
APPLIED ACOUSTICS, 2016, 113 :1-6
[9]   Design optimization of a cellular-type noise insulation panel to improve transmission loss at low frequency [J].
Kim, Hyun-Guk ;
Goo, Seongyeol ;
Jung, Jaesoon ;
Wang, Semyung .
JOURNAL OF SOUND AND VIBRATION, 2019, 447 :105-119
[10]   Testing a class of non-Kerr metrics with hot spots orbiting SgrA* [J].
Liu, Dan ;
Li, Zilong ;
Bambi, Cosimo .
JOURNAL OF COSMOLOGY AND ASTROPARTICLE PHYSICS, 2015, (01)