Development of a Multi-Well Pairing System for Groundwater Heat Pump Systems

被引:6
作者
Kim, Hongkyo [1 ]
Nam, Yujin [1 ]
Bae, Sang Mu [1 ]
Jeoun, Oun [2 ]
机构
[1] Pusan Natl Univ, Dept Architectural Engn, 2 Busandaehak Ro 63, Busan 46241, South Korea
[2] GGK Co Ltd, 69-63 Sansu Ro, Gwangju Si 12737, Gyeonggi Do, South Korea
关键词
groundwater heat pump system (GWHPs); pairing technology; numerical simulation; real-scale experiment; AFFECTED ZONE TAZ; GWHP SYSTEM; FLOW;
D O I
10.3390/en11123485
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Groundwater heat pump systems (GWHPs) can achieve higher coefficient of performance (COP) than air-source heat pump systems by using the relatively stable temperature of groundwater. Among GWHPs, multi-well systems have lower initial investment costs than conventional closed-loop geothermal systems, because they typically require installation of fewer boreholes for the same building load. However, the performance of GWHPs depends significantly on the groundwater properties, such as groundwater temperature, permeability and water quality. Moreover, pumping and injecting of groundwater during long-term operation may lead to problems such as overflow or clogging of the wells. In order to ensure reliable energy from ground sources, the development of sustainable operation methods for multi-well systems is essential for preventing overflow and well clogging. In this study, we have developed a pairing technology that connects the injection and supply wells through a spillway. This pairing technology can be used to control groundwater levels in wells and can be sustainably operated. To accurately estimate the performance of a multi-well system with the proposed pairing technology, the heating and cooling performance of the developed system was compared to that of a standing column well (SCW) system in a field-scale experiment. Furthermore, the effects of the multi-well pairing system on groundwater levels in the injection well were analyzed by numerical simulation. Moreover, in order to decide the required conditions of the multi-well pairing system, case studies were conducted under various hydraulic conductivity and pumping conditions.
引用
收藏
页数:15
相关论文
共 18 条
[1]   Performance analysis of using mine water from an abandoned coal mine for heating of buildings using an open loop based single shaft GSHP system [J].
Al-Habaibeh, Amin ;
Athresh, Anup P. ;
Parker, Keith .
APPLIED ENERGY, 2018, 211 :393-402
[2]  
Cooper H.H., 1946, EOS T AM GEOPHYS UN, V27, P526, DOI [10.1029/TR027i004p00526, DOI 10.1029/TR027I004P00526]
[3]  
Diersch H.J., 2009, FEFLOW Reference manual
[4]  
Hahn J.-S., 2010, GEOTHERMAL ENERGY, P1
[5]   A Numerical Study on System Performance of Groundwater Heat Pumps [J].
Kim, Jinsang ;
Nam, Yujin .
ENERGIES, 2016, 9 (01)
[6]  
Kwon KS, 2012, J GEOL SOC KOREA, V48, P193
[7]   Groundwater Heat Pump (GWHP) system modeling and Thermal Affected Zone (TAZ) prediction reliability: Influence of temporal variations in flow discharge and injection temperature [J].
Lo Russo, Stefano ;
Gnavi, Loretta ;
Roccia, Emanuele ;
Taddia, Glenda ;
Verda, Vittorio .
GEOTHERMICS, 2014, 51 :103-112
[8]   Development of the thermally affected zone (TAZ) around a groundwater heat pump (GWHP) system: A sensitivity analysis [J].
Lo Russo, Stefano ;
Taddia, Glenda ;
Verda, Vittorio .
GEOTHERMICS, 2012, 43 :66-74
[9]  
배상무, 2017, 한국지열에너지학회논문집, V13, P14, DOI 10.17664/ksgee.2017.13.1.014
[10]   Numerical simulation of ground heat and water transfer for groundwater heat pump system based on real-scale experiment [J].
Nam, Yujin ;
Ooka, Ryozo .
ENERGY AND BUILDINGS, 2010, 42 (01) :69-75