Application of C6F12O/CO2 mixture in 10 kV medium-voltage switchgear

被引:64
作者
Tian, Shuangshuang [1 ]
Zhang, Xiaoxing [1 ]
Xiao, Song [2 ]
Zhang, Ji [2 ]
Chen, Qi [2 ]
Li, Yi [2 ]
机构
[1] Hubei Univ Technol, Hubei Key Lab High Efficiency Utilizat Solar Ener, Wuhan, Hubei, Peoples R China
[2] Wuhan Univ, Sch Elect Engn, Wuhan, Hubei, Peoples R China
基金
中国国家自然科学基金;
关键词
organic compounds; global warming; circuit breakers; electric breakdown; switchgear; load switch cabinet; circuit breaker switch cabinet; power frequency; lightning impulse test; medium-voltage switchgear; electrical equipment; chemical properties; power-frequency breakdown test; electric field; breakdown performance; physical properties; dodecafluoro-2-methylpentan-3-one; voltage; 10; 0; kV; SF6; CO2; INDUSTRIAL GREENHOUSE-GAS; DECOMPOSITION CHARACTERISTICS; DIELECTRIC-PROPERTIES; INSULATION; DISCHARGE; STRENGTH; REPLACE; SF6;
D O I
10.1049/iet-smt.2018.5482
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Due to the high global warming potential (GWP) of SF6, the use of new gases in electrical equipment has drawn increasing attention. Here, the application of environmental-friendly gas dodecafluoro-2-methylpentan-3-one (C6F12O) and CO2 mixture in 10 kV medium-voltage switchgear is studied. First, the basic physical and chemical properties of C6F12O were discussed, and the toxicity and safety of its application in equipment was analysed. Then, the breakdown voltage was measured in the laboratory. The power-frequency breakdown test was carried out with the mixing ratio of 2, 4 and 6% at 0.1 similar to 0.2 MPa, and the influence of utilisation coefficient of electric field on the breakdown performance was analysed. Finally, the appropriate mixing ratio was determined and tested in the load switch cabinet and the circuit breaker switch cabinet, including the power frequency withstand voltage test and the lightning impulse test. The test results show that 4% C6F12O and CO2 meet the standard value tested at a pressure of >0.14 MPa, which has the potential to be used as an insulating gas in a 10 kV switchgear.
引用
收藏
页码:1225 / 1230
页数:6
相关论文
共 34 条
  • [1] Atmospheric Chemistry of (CF3)2CF-CN: A Replacement Compound for the Most Potent Industrial Greenhouse Gas, SF6
    Andersen, Mads P. Sulbaek
    Kyte, Mildrid
    Andersen, Simone Thirstrup
    Nielsen, Claus J.
    Nielsen, Ole John
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2017, 51 (03) : 1321 - 1329
  • [2] Bertolini Massimo, 2009, International Journal of Decision Sciences, Risk and Management, V1, P180, DOI 10.1504/IJDSRM.2009.031117
  • [3] Transport properties of CF3I thermal plasmas mixed with CO2, air or N2 as an alternative to SF6 plasmas in high-voltage circuit breakers
    Cressault, Y.
    Connord, V.
    Hingana, H.
    Teulet, Ph
    Gleizes, A.
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2011, 44 (49)
  • [4] Electron attachment, ionization and drift in c-C4F8
    de Urquijo, J
    Basurto, E
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2001, 34 (09) : 1352 - 1354
  • [5] Analysis of the Insulation Characteristics of C3F8 Gas Mixtures with N2 and CO2 using Boltzmann Equation Method
    Deng, Yunkun
    Li, Bing
    Xiao, Dengming
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (06) : 3253 - 3259
  • [6] Analysis of the insulation characteristics of CF3I gas mixtures with Ar, Xe, He, N2, and CO2 using Boltzmann equation method
    Deng, Yunkun
    Xiao, Dengming
    [J]. JAPANESE JOURNAL OF APPLIED PHYSICS, 2014, 53 (09)
  • [7] Goshima H, 2001, GASEOUS DIELECTRICS IX, P359
  • [8] ALTERNATIVE INSULATION GAS FOR MEDIUM-VOLTAGE SWITCHGEAR
    Hyrenbach, Maik
    Zache, Sebastian
    [J]. 2016 PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE EUROPE (PCIC EUROPE), 2016,
  • [9] Green Gas to Replace SF6 in Electrical Grids
    Kieffel, Yannick
    Irwin, Todd
    Ponchon, Philippe
    Owens, John
    [J]. IEEE POWER & ENERGY MAGAZINE, 2016, 14 : 32 - 39
  • [10] Koch D., 2003, SCHNEIDER ELECT CASH, V188, P1