Performance evaluation of an indirect pre-cooling evaporative heat exchanger operating in hot and humid climate

被引:97
作者
Cui, X. [1 ]
Chua, K. J. [1 ,2 ]
Islam, M. R. [2 ]
Ng, K. C. [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, Singapore 117576, Singapore
[2] Natl Univ Singapore, Engn Sci Programme, Singapore 117575, Singapore
关键词
Air conditioning; Mathematical model; Heat and mass transfer; Condensation; Indirect evaporative cooling; MASS-TRANSFER; COOLING SYSTEMS; AIR COOLERS; FLOW; CONDENSATION; FEASIBILITY; STRATEGIES; RECOVERY; MODEL; CYCLE;
D O I
10.1016/j.enconman.2015.02.025
中图分类号
O414.1 [热力学];
学科分类号
摘要
A hybrid system, that combines an indirect evaporative heat exchanger (IEHX) and a vapor compression system, is introduced for humid tropical climate application. The chief purpose of the IEHX is to pre-cool the incoming air for vapor compression system. In the IEHX unit, the outdoor humid air in the product channel may potentially condense when heat is exchanged with the room exhaust air. A computational model has been developed to theoretically investigate the performance of an IEHX with condensation from the product air by employing the room exhaust air as the working air. We validated the model by comparing its temperature distribution and predicted heat flux against experimental data acquired from literature sources. The numerical model showed good agreement with the experimental findings with maximum average discrepancy of 9.7%. The validated model was employed to investigate the performance of two types of IEHX in terms of the air treatment process, temperature and humidity distribution, cooling effectiveness, cooling capacity, and energy consumption. Simulation results have indicated that the IEHX unit is able to fulfill 47% of the cooling load for the outdoor humid air while incurring a small amount of fan power. Consequently, the hybrid system is able to realize significant energy savings. (c) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:140 / 150
页数:11
相关论文
共 39 条
[1]   Performance evaluation of an indirect evaporative cooler under controlled environmental conditions [J].
Ahmad, Aftab ;
Rehman, Shafiqur ;
Al-Hadhrami, Luai M. .
ENERGY AND BUILDINGS, 2013, 62 :278-285
[2]   Numerical analysis of selected evaporative exchangers with the Maisotsenko cycle [J].
Anisimov, Sergey ;
Pandelidis, Demis ;
Danielewicz, Jan .
ENERGY CONVERSION AND MANAGEMENT, 2014, 88 :426-441
[3]  
[Anonymous], 2013, COMSOL MULT REF MAN
[4]  
[Anonymous], 2008, ASHRAE HDB HVAC SYST
[5]  
[Anonymous], 2009, ASHRAE Handbook|Fundamentals
[6]   A comparative study on energetic, exergetic and environmental performance assessments of novel M-Cycle based air coolers for buildings [J].
Caliskan, Hakan ;
Dincer, Ibrahim ;
Hepbasli, Arif .
ENERGY CONVERSION AND MANAGEMENT, 2012, 56 :69-79
[7]   Achieving better energy-efficient air conditioning - A review of technologies and strategies [J].
Chua, K. J. ;
Chou, S. K. ;
Yang, W. M. ;
Yan, J. .
APPLIED ENERGY, 2013, 104 :87-104
[8]   Fundamental formulation of a modified LMTD method to study indirect evaporative heat exchangers [J].
Cui, X. ;
Chua, K. J. ;
Islam, M. R. ;
Yang, W. M. .
ENERGY CONVERSION AND MANAGEMENT, 2014, 88 :372-381
[9]   Numerical simulation of a novel energy-efficient dew-point evaporative air cooler [J].
Cui, X. ;
Chua, K. J. ;
Yang, W. M. .
APPLIED ENERGY, 2014, 136 :979-988
[10]   Experimental investigation of heat recovery system for building air conditioning in hot and humid areas [J].
Delfani, Shahram ;
Pasdarshahri, Hadi ;
Karami, Maryam .