Line measurement of positive, negative and zero sequence parameters of transmission lines with mutual inductance

被引:0
|
作者
Chen, Xiangyi [1 ]
Chen, Yunping [1 ]
Li, Chunyan [1 ]
Tang, Cheng [1 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
关键词
electromagnetic theory; mutual inductance; negative sequence parameter; power system; positive sequence parameter; transmission line measurements; zero sequence parameter;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Positive and negative-sequence usually are ignored only zero-sequence considered on line measurement of the parameters of transmission lines with mutual inductance. This is based on the assumption that distance between phases is much less than the distance between lines. However, for multi-circuits lines on the same tower with strong electromagnetic coupling, the assumption conditions are not met. In this paper the existence of Positive, Negative and Zero-Sequence (PNZS) mutual impedance is proposed in the case that distance between phases is not less than distance between lines. For the first time, the method to calculate the PNZS mutual inductance is studied based on electromagnetic theory. The results of a practical example indicate that positive and negative-sequence affect the line measurement of transmission lines with mutual impedance parameters positively, but the influence is small, and they can be neglected in most cases. So the research provides fundamental basis on engineering application.
引用
收藏
页码:1337 / 1342
页数:6
相关论文
共 50 条
  • [41] MEASUREMENT OF INDUCTANCE OF TRANSMISSION LINES-A CORRECTION TO BE APPLIED TO BRIDGE READINGS
    EDWARDS, RJ
    POST OFFICE ELECTRICAL ENGINEERS JOURNAL, 1966, 58 : 249 - &
  • [42] Online measuring of zero-sequence parameters for coupled double-circuit transmission line
    Liang, Z. (Zhiruil@sohu.com), 1600, Electric Power Automation Equipment Press (33):
  • [43] Impacts of overhead ground wire grounding modes on zero-sequence parameters of transmission line
    Peng, Xiangyang
    Hu, Wei
    Mao, Xianyin
    Wang, Yu
    Wang, Jianguo
    Dianwang Jishu/Power System Technology, 2014, 38 (05): : 1302 - 1309
  • [44] New method of measuring the zero-sequence distributed parameters of non-full-line parallel four-circuit transmission lines
    Mou, Hongjiang
    Hu, Zhijian
    Gao, Mingxin
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 139
  • [45] Impact of zero-sequence mutual inductance in UHV Anhui-to-east power transfer lines on phase-earth distance protection
    Zhang, Bo
    Chen, Fufeng
    Wang, Yuting
    Xue, Mingjun
    He, Benteng
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2013, 37 (21): : 94 - 98
  • [46] Transmission line parameters of video delay lines
    Anicin, BA
    IEE PROCEEDINGS-MICROWAVES ANTENNAS AND PROPAGATION, 1999, 146 (05) : 355 - 358
  • [47] Discussion on live line measurement of the parameters of the transmission lines with four-circuit on a tower
    Wuhan High Voltage Research Institution, Wuhan 430074, China
    不详
    不详
    Gaodianya Jishu, 2006, 7 (17-20):
  • [48] New method of measuring the positive sequence parameters of transmission lines under strong interference condition
    Hu, Zhijian
    Liu, Xuefeng
    Yang, Juan
    Li, Chuanqi
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 837 - +
  • [49] New Method of Measuring the Zero Sequence Parameters of Double-Circuit EHV/UHV Transmission Lines
    Li, Chuanqi
    Hu, Zhijian
    Jiang, Meiling
    Zhang, Ziyong
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [50] Estimation of Positive-, Negative-, and Zero-Sequence Current and Voltage Phasors of UIPC VSCs for Short-Circuit Faults in Transmission Lines
    Bahadori, Babak
    Nahavandi, Ali
    Abasi, Mahyar
    ENGINEERING REPORTS, 2025, 7 (02)