New fault location scheme for three-terminal untransposed parallel transmission lines

被引:30
|
作者
Saber, Ahmed [1 ]
Emam, Ahmed [1 ]
Elghazaly, Hany [1 ]
机构
[1] Cairo Univ, Elect Power & Machine Dept, Cairo, Egypt
关键词
Cross-country faults; Evolving faults; Fault location; Phasor Measurement Unit (PMU); DISTANCE RELAYING ALGORITHM; INFERENCE SYSTEM APPROACH; SYNCHROPHASOR MEASUREMENTS; NETWORKS; CLASSIFICATION; VOLTAGES; WAVELETS;
D O I
10.1016/j.epsr.2017.08.038
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a new fault location scheme in the phase-domain for three-terminal untransposed double-circuit transmission lines utilizing synchronized voltage and current measurements obtained by GPS technique. The proposed scheme is derived taking into consideration the distributed line model and the mutual couplings effect between the parallel lines to obtain accurate results. The proposed scheme is derived based on the transmission line theory and Taylor series expansion of the distributed line model parameters. All fault types including normal shunt faults, evolving faults, and cross-country faults can be discriminated from each other and the fault location can be obtained for all fault types. The evolving faults include earth faults occurring at the same location in two phases of one circuit or two phases of different circuits at different fault inception time. While cross-country faults include earth faults occurring at different locations in two phases of one circuit or two phases of different circuits at same or different fault inception time. The proposed scheme is tested under different fault locations, different fault resistances, different fault inception angles, and all fault types including cross-country and evolving faults. Also, the effect of different sampling rate, measurement and synchronization errors, earth resistivity variations, and transmission line parameters errors on the proposed scheme is considered. Simulations studies conducted by MATLAB software demonstrate that the maximum estimation error in fault location does not exceed 3.06%. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:266 / 275
页数:10
相关论文
共 50 条
  • [1] A new scheme for fault location of three-terminal parallel transmission lines without transposer
    Chen, Gonggui
    Cai, Daiying
    Long, Hongyu
    Long, Yi
    Zeng, Xianjun
    Zhou, Ping
    Kang, Peng
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2021, 15 (17) : 2473 - 2487
  • [2] An Iterative Parameter-Free Fault Location Method on Three-Terminal Untransposed Transmission Lines
    Lu, Dian
    Liu, Yu
    Lu, Dayou
    2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
  • [3] Multiple Fault Location in Three-Terminal Transmission Lines
    Ariakia, Hadi
    Emami, Kianoush
    Fernando, Tyrone
    Iu, Herbert
    IECON 2017 - 43RD ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2017, : 345 - 350
  • [4] Asynchronous Fault Location Scheme Based on Voltage Distribution for Three-Terminal Transmission Lines
    Cao, Pulin
    Shu, Hongchun
    Yang, Bo
    Fang, Yi
    Han, Yiming
    Dong, Jun
    Yu, Tao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (05) : 2530 - 2540
  • [5] A new technique, based on voltages, for fault location on three-terminal transmission lines
    Minambres, JF
    Zamora, I
    Mazon, AJ
    Zorrozua, MA
    AlvarezIsasi, R
    ELECTRIC POWER SYSTEMS RESEARCH, 1996, 37 (02) : 143 - 151
  • [6] New technique, based on voltages, for fault location on three-terminal transmission lines
    Basque Country Univ, Bilbao, Spain
    Electr Power Syst Res, 2 (143-151):
  • [8] PMU-based Fault Location Technique for Three-terminal Parallel Transmission Lines with Series Compensation
    Saber, Ahmed
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2020, 48 (4-5) : 410 - 422
  • [9] Fault location for two- and three-terminal parallel lines using synchronized data
    Stamp, Jason
    Girgis, Adly A.
    International Journal of Power and Energy Systems, 1999, 19 (03): : 212 - 217
  • [10] A new fault location scheme for parallel transmission lines using one-terminal data
    Saber, A.
    Zeineldin, H. H.
    EL-Fouly, Tarek H. M.
    Al-Durra, Ahmed
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 135