Power Flow Adjustment Planning Using Phase Shifting Transformers for Long-Term Generation Outages

被引:3
作者
Ogahara, Ryuichi [1 ]
Kawaura, Yuki [1 ]
Iwamoto, Shinichi [2 ]
Kamikawa, Naohiro [3 ]
Namba, Masayuki [3 ]
机构
[1] Waseda Univ, Grad Sch Sci & Engn, Tokyo, Japan
[2] Waseda Univ, Tokyo, Japan
[3] Tokyo Elect Power Co Ltd, Tokyo, Japan
关键词
power system; transmission planning; phase shifting transformer; line flow sensitivity; branch and bound method;
D O I
10.1002/eej.22719
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
High growth in electricity demand during the period of Japan's bubble economy resulted in the construction of many power transmission facilities, including some loop systems. In some loop systems, there is a possibility of considerable power flow differences between heavy and light loads. Significant changes in the power system, such as from damage due to a natural disaster, would likely result in even larger differences and ineffective use of the loop system. Phase shifting transformers (PSTs) are highly efficient equipment for solving such power flow problems and some studies of operation methods using active power flow sensitivity (APFS) have been carried out. Calculating APFS, however, requires using the dc method. Since doing so requires the fulfillment of several assumptions, errors may appear in the calculation results. This paper assumes protracted significant local loss of generation capability (about 20% of total capacity), and examines the resulting load changes in the loop system. We then propose use of PSTs to alleviate load differences among transmission lines, allowing more effective use of the loop system. Specifically, we propose the concepts of APFS and active power flow sensitivity 2 (APFS2). Installing PSTs at optimal locations and operating the PSTs with proper phase angles determined by a branch and bound method, we mitigate loading differences between heavily and lightly loaded transmission lines. The validity of the proposed method is confirmed by using a modified IEEJ EAST 30 model. (C) 2015 Wiley Periodicals, Inc.
引用
收藏
页码:12 / 21
页数:10
相关论文
共 8 条
[1]  
[Anonymous], 1999, IEEJ TECH REP, V754, P10
[2]  
Bresesti P, 2004, 2004 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1 AND 2, P1192
[3]  
Jibiki Takahiro, 2008, Transactions of the Institute of Electrical Engineers of Japan, Part B, V128, P537, DOI 10.1541/ieejpes.128.537
[4]  
Kling W. L., 2004, CIGRE PAR S
[5]  
Konno H., 1982, INTEGER PROGRAMMING, P48
[6]  
Tanaka H, 2007, P 2007 ANN C POW EN
[7]   Phase shifter coordination for optimal transmission capacity using particle swarm optimization [J].
Verboomen, J. ;
Van Hertem, D. ;
Schavemaker, P. H. ;
Spaan, F. J. C. M. ;
Delince, J. -M. ;
Belmans, R. ;
Kling, W. L. .
ELECTRIC POWER SYSTEMS RESEARCH, 2008, 78 (09) :1648-1653