Stability Analysis for the Grid-Connected Single-Phase Asymmetrical Cascaded Multilevel Inverter With SRF-PI Current Control Under Weak Grid Conditions

被引:66
作者
Han, Yang [1 ]
Chen, Hao [1 ]
Li, Zipeng [2 ]
Yang, Ping [1 ]
Xu, Lin [3 ]
Guerrero, Josep M. [4 ]
机构
[1] Univ Elect Sci & Technol China, Sch Mech & Elect Engn, Chengdu 611731, Sichuan, Peoples R China
[2] State Grid Guanghan City Elect Power Supply Branc, Guanghan 618300, Peoples R China
[3] Sichuan Elect Power Res Inst, Chengdu 610072, Sichuan, Peoples R China
[4] Aalborg Univ, Dept Energy Technol, DK-9220 Aalborg, Denmark
基金
中国国家自然科学基金;
关键词
Asymmetrical cascaded H-bridge multilevel inverter (ACHMI); impedance stability criterion; phase-locked loop (PLL); small-signal model; weak grid; POWER CONVERTERS; LOCKED LOOP; SYNCHRONIZATION;
D O I
10.1109/TPEL.2018.2867610
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes the influence of phase-locked loop (PLL) on the stability of LCL-type single-phase grid-connected asymmetrical cascaded H-bridge multilevel inverter (ACHMI) with synchronous reference frame proportional-integral (SRF-PI) grid current control under weak grid scenarios. The ACHMI system is composed of power stage circuit and control system, where the control system contains the dual-loop current control strategy established in the hybrid reference frame, the SRF-PLL, and the hybrid modulation method employed to synthesize the multilevel output voltage. The small-signal model of the whole ACHMI system is first established by using a simple step-by-step derivation method, and then, the small-signal analysis method is adopted to linearize the ACHMI, which is then utilized to derive the impedance model of the ACHMI system. Furthermore, an improved impedance stability criterion is derived, which is then employed to analyze the system stability. By using this criterion, the stability of the ACHMI can be evaluated with the variation of the bandwidth of PLL, the output power factor angle of the ACHMI, and the amplitude of the grid current reference signal under weak grid conditions. In this paper, a systematic design procedure for the optimal selection of the PI controller of the PLL is presented, which guarantees the steady-state performance and dynamic response of the ACHMI system. With this design method, the dual-loop current control and PLL can be taken into account simultaneously when analyzing the stability margin of the ACHMI. Finally, the simulation and experimental results from a down-scaled grid-connected ACHMI prototype system are provided to confirm the validity of theoretical analysis.
引用
收藏
页码:2052 / 2069
页数:18
相关论文
共 43 条
[1]   Cascade-multi-cell multilevel converter with reduced number of switches [J].
Ajami, Ali ;
Oskuee, Mohammad Reza Jannati ;
Khosroshahi, Mahdi Toopchi ;
Mokhberdoran, Ataollah .
IET POWER ELECTRONICS, 2014, 7 (03) :552-558
[2]   Operational Analysis of Improved Γ-Z-Source Inverter With Clamping Diode and Its Comparative Evaluation [J].
Aleem, Zeeshan ;
Hanif, Moin .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2017, 64 (12) :9191-9200
[3]   Couplings in Phase Domain Impedance Modeling of Grid-Connected Converters [J].
Bakhshizadeh, Mohammad Kazem ;
Wang, Xiongfei ;
Blaabjerg, Frede ;
Hjerrild, Jesper ;
Kocewiak, Lukasz ;
Bak, Claus Leth ;
Hesselbk, Bo .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (10) :6792-6796
[4]   Novel three-phase asymmetrical cascaded multilevel voltage source inverter [J].
Belkamel, Hamza ;
Mekhilef, Saad ;
Masaoud, Ammar ;
Naeim, Mohsen Abdel .
IET POWER ELECTRONICS, 2013, 6 (08) :1696-1706
[5]   Overview of control and grid synchronization for distributed power generation systems [J].
Blaabjerg, Frede ;
Teodorescu, Remus ;
Liserre, Marco ;
Timbus, Adrian V. .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) :1398-1409
[6]   Impedance Modeling and Analysis of Grid-Connected Voltage-Source Converters [J].
Cespedes, Mauricio ;
Sun, Jian .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) :1254-1261
[7]  
Céspedes M, 2012, APPL POWER ELECT CO, P754, DOI 10.1109/APEC.2012.6165904
[8]   Impedance-Phased Dynamic Control Method for Grid-Connected Inverters in a Weak Grid [J].
Chen, Xin ;
Zhang, Yang ;
Wang, Shanshan ;
Chen, Jie ;
Gong, Chunying .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (01) :274-283
[9]   Analysis of Phase-Locked Loop Low-Frequency Stability in Three-Phase Grid-Connected Power Converters Considering Impedance Interactions [J].
Dong, Dong ;
Wen, Bo ;
Boroyevich, Dushan ;
Mattavelli, Paolo ;
Xue, Yaosuo .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2015, 62 (01) :310-321
[10]   Asymmetrical Cascaded Multilevel Inverter Based on Transistor-Clamped H-Bridge Power Cell [J].
Elias, Mohamad Fathi Mohamad ;
Abd Rahim, Nasrudin ;
Ping, Hew Wooi ;
Uddin, Mohammad Nasir .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2014, 50 (06) :4281-4288