Common faults and their impacts for rooftop air conditioners

被引:132
作者
Breuker, MS [1 ]
Braun, JE
机构
[1] DukeSolut, Indianapolis, IN USA
[2] Purdue Univ, Sch Mech Engn, W Lafayette, IN 47907 USA
来源
HVAC&R RESEARCH | 1998年 / 4卷 / 03期
关键词
D O I
10.1080/10789669.1998.10391406
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper identifies important faults and their performance impacts for rooftop air conditioners. The frequencies of occurrence and the relative costs of service for different faults were estimated through analysis of service records. Several of the important and difficult to diagnose refrigeration cycle faults were simulated in the laboratory. Also, the impacts an several performance indices were quantified through transient testing for a range of conditions and fault levels. The transient test results indicated that fault detection and diagnostics could be performed using methods that incorporate steady-state assumptions and models. Furthermore, the fault testing led to a set of generic rules for the impacts of faults on measurements that could be used for fault diagnoses. The average impacts of the faults on cooling capacity and coefficient of performance (COP) were also evaluated. Based upon the results, all of the faults are significant at the levels introduced, and should be detected and diagnosed by an FDD system. The data set obtained during this work was very comprehensive, and was used to design and evaluate the performance of an FDD method (Breuker 1997a) that will be reported in a future paper.
引用
收藏
页码:303 / 318
页数:16
相关论文
共 19 条
  • [1] ASHRAE, 1993, ASHRAE Handbook, Fundamentals, VI-P
  • [2] BRAUKER MS, 1997, HL989 PURD U RW HERR
  • [3] BREUKER MS, 1997, THESIS PURDUE U
  • [4] BULTMAN DH, 1993, P NAT HEAT TRANSF C
  • [5] ONLINE FAILURE DIAGNOSIS FOR COMPRESSION REFRIGERATION PLANTS
    GRIMMELIUS, HT
    WOUD, JK
    BEEN, G
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (01): : 31 - 41
  • [6] INATSU H, 1992, P SOC AUT ENG
  • [7] JANAUSHEK N, 1995, COMMUNICATION
  • [8] KRAFTHEFER B, 1987, ASHRAE T, V93, P1458
  • [9] Kumamaru T., 1991, Proceedings IECON '91. 1991 International Conference on Industrial Electrlnics, Control and Instrumentation (Cat. No.91CH2976-9), P131, DOI 10.1109/IECON.1991.239316
  • [10] MCKELLAR MG, 1987, THESIS PURDUE U