摘要
Two-phase flow patterns and heat transfer characteristics of R410A-oil mixture flow boiling inside a straight smooth tube with the outside diameter of 7.0 mm were investigated experimentally. The experimental conditions include the evaporation temperature of 5 degrees C, the mass flux from 200 to 400 kg m(-2) s(-1), the heat flux from 7.56 to 15.12 kW m(-2), the inlet vapor quality from 0.2 to 0.7, nominal oil concentration from 0% to 5%. The test results show that the heat transfer coefficient of R410A-oil mixture increases with mass flux of refrigerant-oil mixture; the presence of oil enhances the heat transfer at the range of low and intermediate vapor qualities; there is a peak of local heat transfer coefficient at about 2-4% nominal oil concentration at higher vapor qualities, and the peak shifts to lower nominal oil concentration with the increasing of vapor qualities; higher nominal oil concentration gives more detrimental effect at high vapor qualities. The flow pattern map of R410A-oil mixture was developed based on refrigerant-oil mixture properties, and the observed flow patterns match well with the flow pattern map. New correlation to predict the local heat transfer of R410A-oil mixture flow boiling inside the straight smooth tube was developed based on flow patterns and local properties of refrigerant-oil mixture, and it agrees with 90% of the experiment data within the deviation of +/-25%. (C) 2007 Elsevier Inc. All rights reserved.
引用
收藏
页码:857 / 869
页数:13
相关论文
共 43 条
[1]  
*ASHRAE STAND COMM, 1996, STAND METH MEAS PROP
[2]  
Cawte H, 1996, INT J ENERG RES, V20, P663, DOI 10.1002/(SICI)1099-114X(199608)20:8<663::AID-ER181>3.0.CO
[3]  
2-M
[4]  
EBISU T, 1998, ASHRAE T, V19, P556
[5]  
Eckels S.J., 1994, ASHRAE Transcr., V100, P265
[6]  
Eckels S.J., 1998, ASHRAE Transcr., V104, P366
[7]  
Eckels S.J, 1998, ASHRAE Transcr., V104, P376
[8]  
FUKUSHIMA T, 1990, INT REFR C PURD, P196
[9]   Condensation and evaporation heat transfer of R410A inside internally grooved horizontal tubes [J].
Goto, M ;
Inoue, N ;
Ishiwatari, N .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (07) :628-638
[10]   Flow-boiling of R22, R134a, R507, R404A and R410A inside a smooth horizontal tube [J].
Greco, A ;
Vanoli, GP .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2005, 28 (06) :872-880