Turbulence correction for thermal comfort calculation

被引:28
作者
Koskela, H [1 ]
Heikkinen, J [1 ]
Niemelä, R [1 ]
Hautalampi, T [1 ]
机构
[1] Finnish Inst Occupat Hlth, FIN-20500 Turku, Finland
关键词
air speed; air velocity; turbulence intensity; draught risk; thermal comfort;
D O I
10.1016/S0360-1323(00)00002-0
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermal comfort in ventilated spaces depends mainly on air temperature, air speed and turbulence intensity. Mean air speed is commonly measured with omnidirectional hot sphere sensors, whereas directionally sensitive measurement instruments and CFD-simulations normally give the mean velocity vector. The magnitude of the mean velocity vector in turbulent room air flows can be much lower than the mean air speed due to different time averaging processes. This paper studies the difference both experimentally and theoretically as a function of turbulence intensity. A correction method was developed for calculating estimates for omnidirectional mean air speed and turbulence intensity from directional air velocity data. The method can be applied to the calculation of draught risk and thermal comfort from CFD-simulation results. (C) 2000 Elsevier Science Ltd. All rights reserved.
引用
收藏
页码:247 / 255
页数:9
相关论文
共 15 条
[1]   MEASUREMENTS WITH A PULSED-WIRE AND A HOT-WIRE ANEMOMETER IN HIGHLY TURBULENT WAKE OF A NORMAL FLAT-PLATE [J].
BRADBURY, LJS .
JOURNAL OF FLUID MECHANICS, 1976, 77 (OCT8) :473-497
[2]  
Chen Q., 1992, DATABASE ASSESSING I
[3]   Predicting air flow and thermal comfort in an indoor environment under different air diffusion models [J].
Chung, KC ;
Lee, CY .
BUILDING AND ENVIRONMENT, 1996, 31 (01) :21-26
[4]   AIR TURBULENCE AND SENSATION OF DRAFT [J].
FANGER, PO ;
MELIKOV, AK ;
HANZAWA, H ;
RING, J .
ENERGY AND BUILDINGS, 1988, 12 (01) :21-39
[5]   Measurements of air flow characteristics in a full-scale clean room [J].
Hu, SC ;
Wu, YY ;
Liu, CJ .
BUILDING AND ENVIRONMENT, 1996, 31 (02) :119-128
[6]  
ISO, 1994, 7730 ISO
[7]  
KOFOED P, 1993, P IND AIR 93 HELS FI, V5, P235
[8]  
KOSKELA H, 1996, P IND AIR 96 NAG JAP, P845
[9]  
KROGSTAD PA, 1985, AMSTERDAM EUROMECH, P202
[10]  
Lemaire A.D., 1993, ROOM AIR CONTAMINANT