An experimental and numerical analysis of the thermal performance of double-layer Trombe walls

被引:3
作者
Ma, Qingsong [1 ,2 ]
Wang, Xin [2 ]
Chen, Xiaofei [2 ]
Fukuda, Hiroatsu [3 ]
Gao, Weijun [1 ,3 ]
Wei, Xindong [4 ]
机构
[1] Qingdao Univ Technol, iSMART, Qingdao 266033, Peoples R China
[2] Qingdao Univ Technol, Coll Architecture & Urban Planning, Qingdao, Peoples R China
[3] Univ Kitakyushu, Dept Architecture, Kitakyushu, Fukuoka, Japan
[4] Jilin Jianzhu Univ, Sch Environm & Municipal Engn, Changchun, Peoples R China
关键词
Trombe walls; ventilation; energy performance; THERB for HAM; heat utilization; SYSTEMS;
D O I
10.1080/15567036.2021.1939463
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In this paper, we propose a new intelligent temperature-controlled ventilated double-layer Trombe wall system for cold climate zones. This system consists of an insulation layer, an inner air channel, a massive wall, an outer air channel and a glazing plate. By changing the ventilated condition of inner and outer air layers, this system further contains three types of Trombe wall structures: inner ventilated (type 1), double ventilated (type 2) and outer ventilated (type 3). This system can automatically control the heat convection between rooms and Trombe walls, according to changes of air channel temperature that is affected by the local weather condition. Thereby, this system can avoid the problem of indoor heat loss at night and indoor overheating during the day. The main objectives of this paper are: 1) to compare the energy consumption of different types with the same thickness of inner and outer air layers; 2) to compare the thermal energy performance of the same type with different thickness of inner and outer air layers; and 3) to optimize the thickness of the inner and outer air layers of the three types of Trombe wall. Long-term experiments were conducted to investigate the heating potential of ventilated Trombe walls in Qingdao (cold climate zone), China. The thermal energy efficiency of three types of Trombe walls was compared and calculated using THERB for HAM software. The measured results demonstrated that the room temperature is always lower than the outer air channel temperature of the Trombe wall, and the heat of the Trombe wall is not fully utilized. Type 2 presents the best energy efficiency, followed by type 3 and type 1. For all types, when the outer air channel depth is greater than the inner air channel depth, the energy efficiency is improved. Affected by dry-bulb temperature and global horizontal irradiation, the monthly heating load of three types of Trombe walls in ascending order are April, November, March, February, December and January. Compared with a house without a ventilated Trombe wall, the heating efficiency of type 2, type 3 and type 1 is 32.6%, 30.5%, and 23.8%, respectively.
引用
收藏
页码:8909 / 8924
页数:16
相关论文
共 42 条
  • [1] [Anonymous], 2010, P SOL EN SOC ANN C 2
  • [2] Birkeland J., 2012, POSITIVE DEV VICIOUS
  • [3] Review of passive solar heating and cooling technologies
    Chan, Hoy-Yen
    Riffat, Saffa B.
    Zhu, Jie
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2010, 14 (02) : 781 - 789
  • [4] Study and analysis of air flow characteristics in Trombe wall
    Du, Li
    Ping, Lin
    Yongming, Chen
    [J]. RENEWABLE ENERGY, 2020, 162 : 234 - 241
  • [5] Experimental study on thermal performance of an integrated PCM Trombe wall
    Duan, Shuangping
    Wang, Lin
    Zhao, Zhiqiang
    Zhang, Chengwang
    [J]. RENEWABLE ENERGY, 2021, 163 : 1932 - 1941
  • [6] Effective use of venetian blind in Trombe wall for solar space conditioning control
    Hong, Xiaoqiang
    Leung, Michael K. H.
    He, Wei
    [J]. APPLIED ENERGY, 2019, 250 : 452 - 460
  • [7] An experimental and numerical analysis of a novel water blind-Trombe wall system
    Hu, Zhongting
    Zhang, Sheng
    Hou, Jingxin
    He, Wei
    Liu, Xianghua
    Yu, Cairui
    Zhu, Jian
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2020, 205
  • [8] A review on the application of Trombe wall system in buildings
    Hu, Zhongting
    He, Wei
    Ji, Jie
    Zhang, Shengyao
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 70 : 976 - 987
  • [9] Numerical and experimental study on the performance of a Photovoltaic Trombe wall system with Venetian blinds
    Islam, Nazrul
    Irshad, Kashif
    Zahir, Md Hasan
    Islam, Saiful
    [J]. ENERGY, 2021, 218 (218)
  • [10] An improved approach for the application of Trombe wall system to building construction with selective thermo-insulation fa‡ades
    Ji Jie
    Luo ChengLong
    Sun Wei
    Yu HanCheng
    He Wei
    Pei Gang
    [J]. CHINESE SCIENCE BULLETIN, 2009, 54 (11): : 1949 - 1956