Investigation on distribution of electro-thermal coupled field and improved design of ±1100 kV converter valve-side bushing

被引:20
|
作者
Liu, Xuandong [1 ]
Chen, Ming [1 ]
Liang, Chengjun [1 ]
Tang, Hao [2 ]
Zhang, Qiaogen [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] China Elect Power Res Inst, Beijing 100085, Peoples R China
关键词
temperature distribution; paper; thermal conductivity; electric fields; insulation; HVDC power convertors; finite element analysis; resins; bushings; internal fields; external electric fields; electro-thermal coupled field; <plus; minus>1100 kV converter valve-side; uneven temperature distribution; severe electric field distortion; high-ambient-temperature; typical bushing; bushing designs; resin-impregnated paper material; voltage; 1100; 0; kV; HIGH-THERMAL-CONDUCTIVITY; TEMPERATURE DISTRIBUTION; RESIN; PREDICTION; WINDINGS;
D O I
10.1049/iet-smt.2019.0089
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Compared to bushings with lower voltage levels, the +/- 1100 kV converter valve-side bushing has thicker radial insulation and longer axial insulation resulting in a more uneven temperature distribution and more severe electric field distortion, especially under high-ambient-temperature and high-current conditions. Improving the distribution of the electro-thermal coupled field of the bushing is critical for the safe operation of converter transformers. This study discusses the distribution of electro-thermal coupled field of a typical bushing and proposes a new method to evaluate the conductivity of multiple capacitor layers under inhomogeneous axial temperatures. The effects of four bushing designs are investigated as per the adjustment of the capacitor screen structure, the replacement of the current-carrying structure, and the modification of resin-impregnated paper material. The results show that merely adjusting the capacitor screens is not feasible due to size limitations. By decreasing heat accumulation, adopting a single-tube structure and increasing the thermal conductivity of resin-impregnated paper material can reduce electric field distortion to a certain extent. Unlike the other three methods, hierarchically controlling the material resistance effectively balances the internal and external electric fields. Simulation results demonstrate the feasibility of these methods to improve the distribution of the electro-thermal coupled field in the bushing.
引用
收藏
页码:188 / 197
页数:10
相关论文
共 24 条
  • [1] Temperature-dependent electric field distribution in ±800 kV valve-side bushing insulation for a converter transformer
    Du, Boxue
    Sun, Hanlei
    Jiang, Jinpeng
    Kong, Xiaoxiao
    Yang, Wei
    HIGH VOLTAGE, 2021, 6 (01) : 106 - 115
  • [2] Research on the dynamic characteristics of electric field distribution of the ± 1100 kV Ultra high voltage converter transformer valve-side bushing using weakly ionised gas conductance model
    Wang, Qingyu
    Liu, Peng
    Tian, Huidong
    Xie, Gengsheng
    Peng, Zongren
    Yang, Xi
    HIGH VOLTAGE, 2022, 7 (02) : 288 - 301
  • [3] Analysis of the influence of configuration parameters on the electric field distribution of the main insulation structure of valve-side winding of converter transformer considering electro-thermal coupling
    Yang, Lijun
    Cheng, Zhidong
    Cheng, Li
    Liao, Ruijin
    IET ELECTRIC POWER APPLICATIONS, 2024, 18 (12) : 1948 - 1964
  • [4] Influence of material volume conductivity on electric field and surface charge of RIP valve-side bushing core under DC electro-thermal coupling stress
    Chen, Ming
    Liu, Xuandong
    Sun, Yuhan
    Wu, Zhicheng
    Tang, Hao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (01) : 164 - 171
  • [5] Electro-Thermal Coupling Field Simulation of Converter Transformer Valve Side Bushings
    Wang, Qingyu
    Xie, Gengsheng
    Tian, Huidong
    Peng, Zongren
    Yang, Xi
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2021, 16 (02) : 248 - 258
  • [6] Simulation and Experimental Analysis of μ800 kV Converter Transformer Valve-side Bushing Under High Current
    Xie G.
    Shi S.
    Wang Q.
    Wang Q.
    Liu P.
    Peng Z.
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (03): : 994 - 1002
  • [7] Optimization of electric thermal flow field in valve-side bushing of converter transformer based on capillary wick heat pipe
    Li, Minjie
    Liu, Xuandong
    Shang, Gaoyi
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2024, 28 (09): : 1 - 10
  • [8] Design and Optimization Analysis of Water Cooling Heat Dissipation for the Valve-side Bushing of Converter Transformer
    Shi S.
    Liu S.
    Xie G.
    Wang Q.
    Wang Q.
    Liu P.
    Peng Z.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (12): : 4861 - 4870
  • [9] Thermal Performance and Insulation Structure Design of. 400kV Valve Side Bushing of Converter
    Zhang Shiling
    Gong Lin
    2020 INTERNATIONAL SYMPOSIUM ON ENERGY ENVIRONMENT AND GREEN DEVELOPMENT, 2021, 657
  • [10] Insulation structure design of valve side bushing of ± 400 kV converter transformer
    Zhang S.
    Peng Z.
    Ning X.
    Tian H.
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2021, 41 (06): : 199 - 206